DeviceNet Communications Cables Wiring
• Using the Connector Provided with the DeviceNet Communications Unit
for a Multidrop Connection (Using Thin Cables)
• When using Thin Cables for a multidrop connection, two wires of the
same color can be inserted into the one hole.
Crimp the two lines together that are to be inserted into the same hole us-
ing a special crimp terminal, as shown in the following diagram.
Crimp Terminal for Two Lines
Crimp terminal
Lines
We recommend the following crimp terminals and crimp tools.
Crimp terminal
Phoenix Contact
Model: AI-TWIN2×0.5-8WH (product code
3200933)
Section 3-3
Crimp tool
Phoenix Contact
Model: UD6 (product code 1204436)
3-17