3.2
SPECIFICATIONS
Maximum operating pressure
(with valve shut off)
Operating temperature range of fluid
Storage temperature range
Materials used
3.3
NOZZLE COUPLINGS
NH (National Hose) threads are standard on all nozzles. Other threads such as NPSH (National Pipe Straight Hose) may be specified at
time of order.
CAUTION
CAUTION
3.4
USE WITH SALT WATER
Use with salt water is permissible provided the equipment is thoroughly cleaned with fresh water after each use. The service life of the
equipment may be shortened due to the effects of corrosion, and is not covered under warranty.
©Copyright Task Force Tips LLC 2002-2024
Mismatched or damaged waterway connections may cause equipment to leak or uncouple under
pressure. Failure could result in injury. Equipment must be mated to matched connections.
Dissimilar metals coupled together can cause galvanic corrosion that can result in the inability to
uncouple the connection, or complete loss of engagement over time. Failure could cause injury. Per
NFPA 1962, if dissimilar metals are left coupled together, an anti-corrosive lubricant should be
applied to the connection and the coupling should be disconnected and inspected at least
quarterly.
300 psi
33 to 120° F
40 to 150° F
Aluminum 6000 series hard anodized MIL8625 class 3 type
2, stainless steel 300 series, nylon 6-6, nitrile rubber
Table 3.2
6
21 bar
1 to 50° C
-40 to 65° C
LIN-035 May 20, 2024 Rev17
Need help?
Do you have a question about the MID-FORCE and is the answer not in the manual?
Questions and answers