Omron CJ1W-ETN21 - 04-2009 Operation Manual page 236

Ethernet units construction of networks
Table of Contents

Advertisement

Error Log
Error
Meaning
code
03C4
Server connection error
03C5
Mail communications error
03C6
Clock data write error
Detailed error code
1st byte
2nd byte
00: DNS
01: Specified
host does not
01: SMTP
exist
02: POP3
02: No ser-
03: SNTP
vice at speci-
fied host
03: Timeout
04: Closed
unilaterally by
host
05: Cannot
connect
because
account infor-
mation does
not match
06: Host
name resolu-
tion error
07: Transmis-
sion error
08: Recep-
tion error
09: Other
error
F101: Mail too large
F102: Mail received from
non-specified address
F103: Mail subject error
F104: Non-specified com-
mand received
F106: Mail format (header)
error
F107: Mail format (body)
error
F201: Parameter error
F301: Decoding error
F302: File attachment error
(filename error, data format
error, I/O memory write size
error)
F303: No attached file
F304: Non-specified file
attachment received
F305: File attachment too
large
Other: FINS error response
code
0001: Clock data could not
be refreshed because of a
CPU Unit error.
0002: Clock data could not
be refreshed because the
CPU Unit could not write
clock data in that operation
mode.
Correction
Take either of the following mea-
sures.
• Correct the settings for each
server.
• Inspect the communications path
(Ethernet Unit, cable connec-
tions, hub, router, server), and
correct the situation that is caus-
ing the error.
Refer to the Operation Manual,
Construction of Applications: Cre-
ating FINS Applications, and cor-
rect the remote node (i.e., the
application on the personal com-
puter).
Clear the CPU Unit error.
Refer to the Operation Manual,
Construction of Applications:
Automatic Clock Adjustment
Function, and check the operat-
ing conditions.
Section 8-3
EE-
PROM
---
---
---
---
211

Hide quick links:

Advertisement

Table of Contents
loading