Using FINS Applications
CX-Programmer/CX-Integrator
Node number: 1
IP address: 192.168.250.1
FinsGateWay Version 2003
Ethernet port
Ethernet (Network number: none)
136
• Node address:
• IP address:
• Destination port number:
• Keep-alive setting:
3. Starting FinsGateway ETN_UNIT Service
Select ETN_UNIT from Services under the Basic Tab in the FinsGateway
Setup Window, and then click the Start Button.
System Configuration Example 3: Connecting the CX-Programmer Online
Using the FINS/TCP Method
In this example, an online connection is made by FINS/TCP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/TCP method
Ethernet Unit
FINS/TCP method
CX-Programmer's Change PLC Dialog Box
Settings for target PLC (PLC1)'s Change PLC Dialog Box
PLC name
Network classification
Network Tab
Set the remote FINS node address.
Set the remote IP address.
Set the FINS/TCP port number for the remote node.
Normally the PLC's default setting of 9600 should be
specified.
Sets the keep-alive function. Normally this should be
selected.
IP address conversion: Automatic generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Target: PLC1
FINS destination
Network number
Node address
Frame length
Response monitor time
Section 6-5
Setting
PLC1
FinsGateway
0
2
2,000 bytes
2 seconds