Sequence Output Instructions - Omron CJ - REFERENCE MANUAL 10-2009 Reference Manual

Table of Contents

Advertisement

3. Instructions

Sequence Output Instructions

OUT/OUT NOT
Instruction
OUTPUT
OUTPUT NOT
Symbol
Applicable Program Areas
Function block
Area
definitions
Usage
OK
Operands
Operand
---
Operand Specifications
Word addresses
Area
CIO
WR
HR
OUT
OK
OK
OK
OUT NOT
*1 CJ2 CPU Units only.
Flags
There are no flags affected by this instruction.
Function
OUT
If there is no immediate refreshing specification, the status of the execution condition (power flow) is
written to the specified bit in I/O memory. If there is an immediate refreshing specification, the status of
the execution condition (power flow) is also written to the Basic Output Unit's output terminal in addition
to the output bit in I/O memory.
OUT NOT
If there is no immediate refreshing specification, the status of the execution condition (power flow) is
reversed and written to a specified bit in I/O memory. If there is an immediate refreshing specification,
the status of the execution condition (power flow) is reversed and also written to the Basic Output Unit's
output terminal in addition to the output bit in I/O memory.
154
Mnemonic
Variations
OUT
!OUT
OUT NOT
!OUT NOT
OUT
Block program areas
Step program areas
Not allowed
OK
Description
---
AR
T
C
DM
EM
1
1
OK
---
---
OK*
OK*
Function
code
Outputs the result (execution condition) of the
---
logical processing to the specified bit.
Reverses the result (execution condition) of the
---
logical processing, and outputs it to the specified
bit.
Subroutines
OK
Data type
BOOL
Indirect DM/EM
addresses
Con-
stants
@DM
*DM
DR
@EM
*EM
---
---
---
---
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Function
OUT NOT
SFC action or transition
Interrupt tasks
programs
OK
OK
Size
---
Registers
Flags
Pulse
bits
Indirect
IR
TK
CF
using IR
---
OK
---
---
TR
bits
---
OK