Wireless heat detector

Advertisement

PG8932/PG9932 wireless heat detector
Installation and operating instructions
Read this instruction sheet thoroughly before installation and use of the PG8932/PG9932
Introduction
The PG8932/PG9932 is a wireless heat detector with a fixed temperature, a rate of rise heat
sensor, and an internal piezoelectric alarm. The detector is available in 915 and 868 MHz
versions. Only Model PG9932 operating in band 912-919MHz is UL/ ULC listed. Model
PG8932 operating in 868MHz band is CE and UKCA compliant.
Compatible devices
Model PG9932 is compatible with UL/ULC listed control
panels DSC/Tyco models: HS2128, HS2064, HS2032,
HS2016, HS3248, HS3128, HS3032 when using RF
Transceiver HSM2HOST9 or Keypads with integral
transceiver HS2LCDRF(P)9, HS2LCDRFPRO9,
HS2LCDICNRF9(P) and Qolsys IQPanel2, IQHub,
IQPanel4.
Operation
During normal operation, the green LED flashes every 12 seconds.
The detector goes into alarm when the heat level exceeds 135 ºF / 57.5 ºC and automatically
restores when the heat level falls below the threshold. The detector also goes into alarm
when the temperature rapidly increases over a short period of time. During an alarm, the
LED flashes once per second and the sounder emits the evacuation temporal pattern.
Detector trouble
If the detector has a general fault, the yellow LED blinks once every four seconds and the
detector emits a chirp every 48 seconds. After four hours, the panel displays a fire trouble
message.
Table: Detector and Status Indication
Status
LEDs
Normal
Green flash every 12 seconds
Heat Alarm Red flash every 1 second
Heat Test
Red flash every 1 second
Test Alarm
(button
Red flash every 1 second
press)
Detector
Yellow flash every 4 seconds
Trouble
Low Battery Yellow flash every 12 seconds
Power-up
Red, yellow, green, flash sequence
Red, yellow, green flash sequence every
Tamper
12 seconds
Wireless transmissions
A supervisory message is transmitted at 128 s intervals. If the signal is not received, the
control panel determines that the detector is missing.
The detector transmits the following:
Idle (normal operation): The detector is in normal state without any faults or
alarms.
Operating temperature: 32°F to 100°F (0°C to 37.8°C)
Heat Alarm: Active when the detector is above 135°F (57.5°C) or the rate of
rise of temperature is above 15°F/min (8.3°C/min).
Tamper / Tamper Restore: (tamper switch activated) ten-second
Sounder
Off
ANSI S3.41 temporal 3
ANSI S3.41 temporal 3
ANSI S3.41 temporal 3
One chirp every 48 seconds
One chirp every 48 seconds
(press button to hush for 12 hours)
One chirp at the end of the power-up
sequence
Off

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PG8932 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls PG8932

  • Page 1 Red flash every 1 second ANSI S3.41 temporal 3 The PG8932/PG9932 is a wireless heat detector with a fixed temperature, a rate of rise heat press) sensor, and an internal piezoelectric alarm. The detector is available in 915 and 868 MHz Detector versions.
  • Page 2: Battery Installation And Replacement

    1. Twist the detector counterclockwise to remove the detector The PG8932/PG9932 wireless heat detector shall be installed and used within an from its mounting base. To remove the battery, carefully environment that provides the pollution degree max 2 and over voltages category II in non- lift it from the + end using a flathead screwdriver.
  • Page 3: Testing The Detector

    5. Select the desired zone number. Mount detector backplate 6. Configure any device parameters that are required. NOTE: The detector should only be installed by a service person. 7. Mount and test the detector. Once a suitable location is found, mount the detector backplate. Install the mounting base on the ceiling or on the wall (if local ordinances permit) using screw locations as required.
  • Page 4: Diagnostic Test

    CAUTION: The diagnostic test cannot be performed when the tamper is open. detector. If you are planning renovations or repainting, take precautions to avoid To perform a detector test, press and hold the Test button for 4 seconds. When the button is dust, paint, or chemical contamination of the detector.
  • Page 5: End User License Agreement

    warning or protection. The Product, properly installed and maintained, only reduces the risk of such BE FIXED AS LIQUIDATED DAMAGES AND NOT AS A PENALTY, AND SHALL BE THE COMPLETE events without warning and it is not a guarantee or insurance that such events will not occur. AND EXCLUSIVE REMEDY AGAINST THE MANUFACTURER.
  • Page 6 THIS EULA. IF YOU DO NOT AGREE TO ALL OF THE TERMS AND CONDITIONS OF THIS EULA, DO NOT OPEN, and will make available to Tyco other legal remedies. DOWNLOAD, INSTALL, COPY OR OTHERWISE USE THE SOFTWARE. Limitations on Reverse Engineering and Derivative Works. You may not reverse engineer, SCOPE OF LICENSE.
  • Page 7 or evaluation period. FROM OR RELATED TO THIS EULA, OR THE USE OF THE SOFTWARE, EXCEED THE AMOUNT Registration of Software. The Software may require registration with Tyco prior to use. If you do not OF FEES YOU PAID TO TYCO OR ITS RESELLER FOR THE SOFTWARE THAT GIVES RISE TO register the Software, this EULA is automatically terminated and you may not use the Software.
  • Page 8: Regulatory Information

    électrique subi, même si le brouillage est susceptible d'en comprom-ettre le fonctionnement. The PG8932/PG9932 wireless heat detector has a recommended service life of 10 years FCC CLASS B DIGITAL DEVICE NOTICE -This equipment has been tested and found to under normal conditions of use.

This manual is also suitable for:

Pg9932

Table of Contents