Installation Instructions
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
When using electrical equipment, basic safety precautions should always be followed including the following:
• CAUTION: Do not join converter connector until installation is complete and AC Power is supplied to
the emergency driver,
• This product is for use with an emergency LED lighting load and supplies a maximum of 7W, 10W or 21W of
power and a maximum voltage of 48VDC in emergency mode for a minimum of 90 minutes.
• To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter
connector of the emergency driver before servicing.
• This emergency driver is suitable for both factory and field installation.
• This product is suitable for use in dry and damp locations.
• The ambient temperature for use is 0°C to 50°C (32°F to 122°F).
• Do not install outdoors.
• An unswitched AC power source of 120/277VAC, 60Hz is required.
• Do not install near gas or electric heaters.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Install in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations.
• Do not use this product for other than intended use.
• Servicing should be performed by qualified service personnel.
• Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
• For use with a metal grounded enclosed wiring system or equivalent.
10070342 REV1 - 03/24
IMPORTANT SAFEGUARDS
SAVE THESE INSTRUCTIONS!
Technical Support
■ (623) 580-8943 ■ technicalsupport@barronltg.com
1
800-533-3948 www.barronltg.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the EXITRONIX LEMDC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for BARRON EXITRONIX LEMDC Series

  • Page 1 LEMDC Series Installation Instructions IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. When using electrical equipment, basic safety precautions should always be followed including the following: • CAUTION: Do not join converter connector until installation is complete and AC Power is supplied to the emergency driver, •...
  • Page 2: Checklist Before Installation

    LEMDC Series Installation Instructions Checklist Before Installation This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED replacements for fluorescent lamps and others. To determine if your luminaire is eligible for field installation, please check the 4 items in the following checklist.
  • Page 3: Installation Instructions

    LEMDC Series Installation Instructions Installation CAUTION: The LEMDC with the polycarbonate case must be installed inside of a luminaire or similar housing which meets the UL requirements for enclosures. The polycarbonate case nor external battery (where applicable) is not suitable for installation outside of the luminaire’s protective enclosure NOTE: Make sure the necessary branch circuit wiring is available.
  • Page 4: Operation

    LEMDC Series Installation Instructions Output Current Setting Model: LEMDC-7-LP-CC Model: LEMDC-10-LP-CC Model: LEMDC-21-LP-CC Micro-Switch Micro-Switch Micro-Switch Current Volts Pwr Current Volts Pwr Current Volts Pwr SW2 SW3 SW4 SW1 SW2 SW3 SW4 SW2 SW3 SW4 SW5: ON, SW6: ON Operation The battery in this unit may not be fully charged.
  • Page 5: Troubleshooting Guide

    LEMDC Series Installation Instructions Troubleshooting Guide STATUS INDICATORS PROBLEM CORRECTIVE ACTION Green Light Red Light ON steady NONE None, Unit is fully charged and working correctly. Flashing Slow NONE None, Unit is in Charging mode. (2s interval) ON Steady NONE None, AC is lost and Unit is in Emergency Discharging mode.
  • Page 6 LEMDC Series Installation Instructions Dimensions LEMDC-7-LP-CC & LEMDC-10-LP-CC& LEMDC-21-LP-CC 1.02” [26.0] 7.56” [192.0] R0.12” [R3.0] 2.00” [50.8] 0.18” [4.7] 7.32” [186.0] 1.18” [30.0] 0.08” [2.0] Battery Pack Dimensions - 7/10W 1.77” [45] 6.93” [176.0] 5.9”±0.4”[150±10] 0.9” [23] Battery Pack Dimensions - 21W 7.8”...