Commissioning; Attaching The Control Unit; Set Valve Type In The Configuration Menu - Bosch THIW Installation And Operating Instructions Manual

Table of Contents

Advertisement

4

Commissioning

4.1

Attaching the control unit

The room thermostat can also be operated independently
without connection to a higher-level control. The range of
functions is then basically limited to displaying the room
temperature and control of the actuator on your heating circuit
manifold according to the specified setpoint temperature in the
manual operating mode (without time program). A connection
to Bosch Bosch EasyControl CT200 can be made at any time in
the future ( Chapter 4.3).
▶ Switch off the electric circuit.
To avoid damage to the appliance:
▶ insert the control panel as parallel to the wall surface as
possible and use the guide elements (amongst others,
notch above the socket). Pay particular attention to the
metal pins on the rear of the control unit.
▶ Insert the control unit [1] into the frame [2] and carefully
press against the flush-mounted appliance [3] until the
frame has a tight fit.
Fig. 20
Attaching the control unit
[1] Control unit with thermostat function
[2] Cover frame
[3] Flush-mounted enclosure with power supply and
switching relay (for 230 V or 24 V voltage supply,
depending on version)
THIW/THIW24 – 6721869244 (2023/06)
3
2
1
0010050860-001
▶ Switch the electric circuit back on.
The appliance performs a function test at start-up and then
shows the room temperature and other display elements.
Furthermore, you can see from the flashing of the status
LED in orange that the pairing mode for connection to
Bosch EasyControl CT200 or SRC 100 RF started
automatically. Without connection, the mode is also ended
automatically after about 6 seconds.
In the first 10 minutes after switching on the mains voltage, the
room thermostat is in start mode and the relay is permanently
activated. In the following 20 minutes, the relay is operated via
a 2-point controller in which the relay is switched on when
falling below the set temperature and switched off accordingly
when it exceeds it. In the following normal operation, the relay
is controlled via a PI control with PWM output.
4.2

Set valve type in the configuration menu

When commissioning for the first time or restoring the factory
settings ( Chapter 6.5), the valve type can be set:
▶ Press the rotary knob and keep it pressed for at least
5 seconds until the configuration menu appears.
▶ Turn the rotary knob to select the valve type:
Valve type "nO" (= normally open; currentless open)
Valve type "nC" (= normally closed, currentless closed)
▶ To confirm the selection: press the rotary selector
If no action is taken on the rotary selector, the configuration
menu is closed after a short time.
If necessary, to correct the valve type:
▶ Call up the configuration menu again.
The configuration menu is no longer available after the room
thermostat has been connected (paired) to Bosch EasyControl
CT200 or SRC 100 RF. In this case, the valve type can be
adjusted via the appliance settings of the app EasyControl or
Bosch HomeCom Easy.
To make it easier to set up the room thermostat via the apps at
a later time and to save having to remove and put the control
unit on again:
▶ attach the QR code sticker included in the scope of delivery
on the room thermostat or on the technical documentation.
Commissioning
47