Electrical Connection - Daikin RN25CXV1 Installation Manual

Hide thumbs Also See for RN25CXV1:
Table of Contents

Advertisement

IMPORTANT: * These values are for information only, they should be checked and selected to comply with the local and/or
** The appropriate voltage range should be checked with data label on the unit.
FDMRN 25/35/50/60C - RN 25/35/50/60C (1PH)
FDMRN 71C - RR 71C (1PH)
Model
Voltage range**
Power supply cable size*
Number of conductors
Interconnection cable size*
Number of conductors
Recommended time delay fuse*
FDMRN 50/60C - RN 50/60C (3PH)
FDMRN 71C - RR 71C (3PH)
Indoor unit
Terminal Block
Model
Voltage range**
Power supply cable size*
Number of conductors
Interconnection cable size*
Number of conductors
Recommended time delay fuse*
1 IM-5CCC-0912(0)-DAIKIN_EN.indd13 13
1 IM-5CCC-0912(0)-DAIKIN_EN.indd13 13

ELECTRICAL CONNECTION

national codes and regulations. They are also subjected to the type of installation and size of conductors.
COMP
L
N
Indoor unit
Terminal Block
N
Indoor (FDMRN)
25C
Outdoor (RN/RR)
25C
Indoor (FDMRN)
Outdoor (RN/RR)
mm
2
2
mm
A
Interconnection cable
COMP
L
N
N
Power Supply Cable
Indoor (FDMRN)
Outdoor (RN/RR)
Indoor (FLRN)
Outdoor (RN/RR)
mm
2
2
mm
A
Interconnection cable
Power Supply Cable
35C
35C
220-240V/1Ph/50Hz+!
220-240V/1Ph/50Hz+!
1.5
1.5
3
3
1.5
1.5
3
3
10
10
COMP
L1
N1
R
S
T
N
50C
50C
220-240V/1Ph/50Hz+!
380-415V/3N~/50Hz+!
1.5
5
1.0
4
6
1-13
COMP
Outdoor unit
Terminal Block
N
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
50C
60C
50C
60C
2.5
2.5
3
3
2.5
2.5
3
3
16
20
Outdoor unit
Terminal Block
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
60C
71C
60C
71C
1.5
1.5
5
5
1.0
1.0
4
4
6
8
71C
71C
2.5
3
2.5
3
20
10/9/12 4:11:10 PM