ELECTRICAL WIRING CONNECTION

• All wires must be firmly connected.
• Make sure all the wire do not touch the refrigerant piping, compressor or any moving parts.
• The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
• In the case when protected pipes are used, use H05VV-U4G for the connecting wire between the indoor unit and the
outdoor unit. Use H07RN-F when protected pipes are not used.
• Make sure no external pressure is applied to the terminal connectors and wires.
• Make sure all the covers are properly fixed to avoid any gap.
• Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Attach insulation sleeve
Round crimp-style terminal
• Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
• Over tightening can damage the terminal screws.
• Do not connect wire of different gauge to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
• For wiring connection between INDOOR and OUTDOOR unit, see Outdoor installation manual and wiring diagram.
Connect wires of the same
gauge to both side.
WARNING
• T ransmission wire must be routed at least
Electric wire
50mm away from the power cable.
• T ransmission wire should be a shielded wire.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
13