INSTALLATION MANUAL R410A SPLIT SERIES MODELS FTNV20JVAK RNV20JVAK FTNV25JVAK RNV25JVAK FTNV30JVAK RNV30JVAK Installation Manual FTYNV20JVAK RYNV20JVAK English R410A Split Series FTYNV25JVAK RYNV25JVAK FTYNV30JVAK RYNV30JVAK FTS20JVAK RS20JVAK FTS25JVAK RS25JVAK FTYS20JVAK RYS20JVAK FTYS25JVAK RYS25JVAK IM-5WMJ(R)-0714(2)-DAIKIN(SASO) Part No.: R08019040624B...
Page 3
OUTLINE AND DIMENSIONS Indoor Unit THE MARK SHOWS PIPING DIRECTION REAR REAR LEFT RIGHT TOP VIEW NAME PLATE SIGNAL RECEIVER TERMINAL BLOCK WITH EARTH SIDE VIEW BOTTOM BOTTOM TERMINAL INDOOR UNIT LOUVER ON/OFF SWITCH FRONT GRILLE FIXED SCREWS (INSIDE) ROOM TEMPERATURE THERMISTOR (INSIDE) FRONT VIEW All dimensions are in mm...
Page 4
Indoor Unit SCREW SCREW SCREW SCREW SCREW Through the wall WM3035J WM3035J hole Ø 65mm SCREW SCREW Gas pipe Liquid pipe Drain hose position INSTALLATION PLATE FTD30/36 All dimensions are in mm Dimension Model FT(Y)NV30 1289 Outdoor Unit All dimensions are in mm Dimension Model R(Y)NV20/25...
Page 5
Outdoor Unit All dimensions are in mm MADE IN MALAYSIA Dimension Model R(Y)NV30 1030 826...
Page 6
INSTALLATION MANUAL This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Page 7
2. Pull out the unit from the other side. • Outdoor Unit 1. After takeoff the bands, pull out the carton box from the top side of the unit. * This product is not designed for re-packing. In case of re-packing, contact to Daikin Dealer.
Page 8
INSTALLATION DIAGRAM Indoor unit Cut thermal insulation pipe to an appropriate length and 75mm or more from ceiling Caulk pipe wrap it with tape, making hole gap sure that no gap is left in the with putty. Front panel insulation pipe’s cut line. Wrap the insulation pipe with the finishing tape from bottom 50mm or more from walls...
Page 9
Condensed Water Disposal Of Outdoor Unit (Heat Pump Unit Only) • There are 2 holes on the base of Outdoor Unit for PLUG condensed water to flow out. Insert the drain elbow to one of the holes. • To install the drain elbow, first insert one portion of the hook to the base (portion A), then pull the drain elbow in BASE the direction shown by the arrow while inserting the other...
Page 10
Bottom or side piping (For FTS/FTYS only) Cut off pipe port cover with a copping saw. ü For bottom piping: On the bottom of the front grille ü For side piping: On the side cover (front grille side and unit side) Apply the blade of the copping saw to the notch, and cut off the pipe port cover along the uneven inner surface.
Page 11
Mounting Installation Plate Mount The Unit Onto The Installation Plate Ensure that the wall is strong enough to withstand the weight Hook the indoor unit onto the upper portion of the installation of the unit. Otherwise, it is necessary to reinforce the wall plate (Engage the two hooks at the rear top of the indoor unit with plates, beams or pillars.
Page 12
REFRIGERANT PIPING Allowable Piping Length and Maximum No. of Bends If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below: Indoor unit Outdoor Unit...
Page 13
REFRIGERANT PIPING Piping Works And Flaring Technique Figure I • Do not use contaminated or damaged copper tubing. If Cutting Copper Tube any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, the system must 1/4t be vacuumed.
Page 14
ELECTRICAL WIRING CONNECTION IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used.
Page 15
• All wires must be fi rmly connected. • All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor. • The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps. •...
Page 16
VACUUMING AND CHARGING Vacuuming is necessary to eliminate all moisture and air from the system. Vacuuming The Piping And The Indoor Unit Except for the outdoor unit which is pre-charged with Refrigerant Piping Allen key Flare nut refrigerant, the indoor unit and the refrigerant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.
Page 17
ADDITIONAL CHARGE The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming is not necessary. If the piping length is more than 7.5m, then use the additional charge value as indicated in the table. Additional refrigerant charge [g] per additional 1m length as tabulated (For R410A models) Indoor FT(Y)NV/FT(Y)S20/25...
Page 18
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling/Heat Pump Unit (For FT(Y)NV20/25 only) Operation COOL/HEAT (BLUE/RED) Cool mode BLUE Heat mode Auto mode in Heating operation Auto mode in Cooling operation BLUE Timer on Sleep mode on Fan mode on BLUE Dry mode on BLUE...
Page 19
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling/Heat Pump Unit (For FT(Y)S20/25 only) Operation COOL/HEAT/TIMER (BLUE/RED/VIOLET) Cool mode BLUE Heat mode Auto mode in Heating operation Auto mode in Cooling operation BLUE Timer on VIOLET Fan mode on BLUE Dry mode on BLUE...
Page 20
AIR CONDITIONER UNIT OPERATION Dry Mode Notes On Flaps And Louvers Angles • When the air humidity is high, the unit can operate in dry • When “SWING button” is selected, the flaps swinging mode. Press <MODE> button and choose <DRY>. range depends on the operation mode.
Page 21
AIR FILTER Open the front panel. Clean or replace each filter. • Hold the panel at the recesses on the main unit (2 recesses See figure. on right and left sides) and lift it until it stops. • When shaking off remaining water, do not wring the filter. Air fi...
Page 22
SERVICE AND MAINTENANCE Service Parts Maintenance Procedures Period Indoor air filter Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm At least once water (below 40°C/104°F) with a neutral cleaning detergent. every 2 weeks. Rinse the filter well and dry before placing it back onto the unit.
Page 23
! CAUTION • Don’t touch the metal parts of the indoor unit. It may cause an injury. • When removing or attaching the front panel, support the panel securely with hand to prevent it from falling. • For cleansing, do not use hot water above 40°C, benzine, gasoline, thinner, nor other volatile oils, polishing compound, scrubbing brushes, nor other hand stuff.
Page 24
INDOOR UNIT 13.0 14.0 16.0 13.0 14.0 OUTDOOR UNIT REFRIGERANT R410A 1.45 2.00 2.60 1.45 2.00 Malaysia COUNTRY OF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT NOTE: This product is not designed for repacking. In case of re-packing, contact to Daikin Dealer.
Page 26
Kita-ku, Osaka, 530-8323 Japan Tokyo offi ce: JR Shinagawa East Bldg., 2-18-1, Konan, P.O.Box 18674, Galleries 4, 11th Floor, Minato-ku, Tokyo, 108-0075 Japan Downtown Jebel Ali, Dubai, UAE. http://www.daikin.com/global/ Importer for Turkey Hürriyet Mahallesi Yakacık D-100 Kuzey Yanyol Caddesi No:49/1-2 Kartal − İstanbul...
Page 27
Kita-ku, Osaka, 530-8323 Japan Tokyo office: JR Shinagawa East Bldg., 2-18-1, Konan, P.O.Box 18674, Galleries 4, 11th Floor, Minato-ku, Tokyo, 108-0075 Japan Downtown Jebel Ali, Dubai, UAE. http://www.daikin.com/global/ Importer for Turkey Hürriyet Mahallesi Yakacık D-100 Kuzey Yanyol Caddesi No:49/1-2 Kartal − İstanbul...