Refrigerant Piping - Daikin RN25CXV1 Installation Manual

Hide thumbs Also See for RN25CXV1:
Table of Contents

Advertisement

Allowable Pipe Length and Elevation
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the fl ow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
Model
Indoor (FDMRN/FDMQN)
Outdoor (RN/RYN)
Max. allowable length, m
Max. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
Model
Indoor (FDMRN/FDMQN)
Outdoor (RR/RQ)
Max. allowable length, m
Max. allowable elevation, m
Liquid pipe size, mm/(in)
Gas pipe size, mm/(in)
NOTE
Be sure to add the proper amount of additional refrigerant, failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for the piping length up to 7.5m.
1 IM-5CCC-0912(0)-DAIKIN_EN.indd11 11
1 IM-5CCC-0912(0)-DAIKIN_EN.indd11 11

REFRIGERANT PIPING

25C
35C
25C
35C
12
5
6.35
6.35
(1/4")
(1/4")
9.52
12.70
(3/8")
(1/2")
71C
71C
90D
15
45
8
25
9.52
9.52
(3/8")
(3/8")
15.88
15.88
(5/8")
(5/8")
1-11
50C
50C
12
15
5
8
6.35
(1/4")
12.70
(1/2")
100C
125C
100D
125D
45
45
25
25
9.52
9.52
(3/8")
(3/8")
15.88
15.88
(5/8")
(5/8")
60C
60C
15
8
6.35
(1/4")
15.88
(5/8")
140C
140D
35
15
9.52
(3/8")
19.05
(3/4")
10/9/12 4:11:10 PM
10/9/12 4:11:10 PM