Insulation Resistance Test - Grundfos SE Service Instructions Manual

Range 56 18-41 kw, 50 hz
Table of Contents

Advertisement

16. Insulation resistance test

Insulation resistance must be measured between common phase wires and the protecting earth (grounding) wire.
in case of DOL: U+V+W - PE
1
U
Test duration
Test voltage
Test voltage upper limit
Test voltage lower limit
Voltage unit
Minimum resistance
Maximum resistance
Resistance unit
96
2
3
V
W
3~
60 [s]
TEST_ISOTEST_DURATION_S
1000
TEST_ISOTEST_VOLTAGE_SETPOINT
980
TEST_ISOTEST_VOLTAGE_TOL_MAX
1020
TEST_ISOTEST_VOLTAGE_TOL_MIN
V
TEST_ISOTEST_VOLTAGE_UNIT
1000
TEST_ISOTEST_RESIST_TOL_MIN
20000
TEST_ISOTEST_RESIST_TOL_MAX
MΩ
TEST_ISOTEST_RESISTANCE_UNIT
in case of Y/D: U1+U2+V1+V2+W1+W2 - PE
1
2
3
U1
V1
W1
3~
6
W2
5
V2
4
U2