Download Print this page

LEGRAND LMSW-605-W Quick Start Manual

Dlm wireless scene switch with ipv6/bluetooth low energy technology

Advertisement

Quick Links

No: 27360 – 10/21 rev. 8
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMSW-605
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Once paired to an LMRC-611 wireless
room controller or LMBC-650 wireless
bridge, this unit is set for Plug n' Go™
operation, adjustment via the DLM
Configuration App is recommended
to meet the local energy code where
installed.
The DLM Wireless 5-Button scene switch is a
wireless battery powered wall switch intended for
operation with wireless room controllers.
Do not apply cleaning solvent directly onto unit.
Apply cleaning solvent onto a cloth, then wipe the
unit to clean it.
NOTE: Installation shall be in accordance with all applicable
regulations, local, and NEC codes
INSTALLING THE BUTTONS
The LMSW-605-W (White) ships with the buttons installed. All
other switch colors ship with our quick install button kit. To install:
Frame
Buttons
Place buttons into Body, then snap-on frame,
pressing down till tabs click.
INSTALLING THE SWITCH
Pull to remove
battery protection tab
before use
Switch Body
Connect ground wire if installing
next to Class 1 power. If not, there
is no need to connect the ground
wire (please comply with local code).
Wattstopper
DLM Wireless Scene Switch with IPv6/Bluetooth
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
SPECIFICATIONS
Power Supply .......................... Battery powered, CR123A Lithium Ion, 3 VDC
Connection to DLM Network ............Wireless via LMRC-611 room controllers
...................................................................................... or LMBC-650
Wireless Radio ........................................ Single, Concurrent 802.15.4 and
....................................................Bluetooth Low Energy, 2.4GHz
Wireless Communication
IPv6 Mesh (6LoWPAN) Range ........................................... up to 60 ft.
Bluetooth low energy Range .............................................. up to 30 ft.
60 ft. max. between LMSW-605 and room controller or bridge
Wireless Encryption ..........................................AES-128 bit symmetric key
Environment ............................................................... For Indoor Use Only
Operating Temperature ...............................32° to 104°F (0° to 40°C)
Storage Temperature .................................23° to 140°F (-5° to 60°C)
Relative Humidity .....................................5 to 95% (non condensing)
Compliance/Regulatory
FCC, RoHS,
Bluetooth certified
UL and cUL listed (E101196)
Patent Pending
BUTTONS AND INDICATORS
Tap when load OFF:
Turn ON to last level
Tap when load ON:
Go to full bright
Press & Hold:
Ramp Up
Tap when load ON:
Turn OFF
Press & Hold:
Ramp Down
LED Color
White
Green, 1 Blink
Blinking Green
Red, 1 Blink
Blinking Red
Blue
®
®
Low Energy Technology
Status/Battery
Life LED
Scene Button (4)
Configuration Button
(behind switch plate)
Function
Unit Boot Up
Config Button Pressed
Push to Pair Mode
In normal operation, if any button is
pressed, indicates low battery
Also blinks if Reset button is pressed
Push n' Learn Mode
Any button or paddle pressed during
normal operation

Advertisement

loading

Summary of Contents for LEGRAND LMSW-605-W

  • Page 1 Relative Humidity ........5 to 95% (non condensing) Compliance/Regulatory INSTALLING THE BUTTONS FCC, RoHS, Bluetooth certified The LMSW-605-W (White) ships with the buttons installed. All UL and cUL listed (E101196) other switch colors ship with our quick install button kit. To install: Patent Pending Switch Body...
  • Page 2: Important Installation Information

    WIRELESS ROOM CONNECTION HYBRID ROOM CONNECTION Line Load LMBR-650 Voltage Examples For networking and LMSW-605 (any relay) managing rooms, Wireless IPv6 Mesh for Room Switched Scene Switch floors, and building networking of DLM Controller Line Voltage (not needed for rooms and devices (LMRC-112) stand-alone rooms) over 6LoWPAN...
  • Page 3 For details on the features and operation, download the DLM Config App User Guide from the Wattstopper web site at : https://www.legrand.us/wattstopper.aspx PLUG N’ GO OPERATION (PNG) Once paired to the switch, all loads are bound to all buttons and the dimmer paddle on Default light the LMSW-605.
  • Page 4 UNIT ADJUSTMENT USING PUSH N’ LEARN NOTE: Although Push n’ Learn™ can be used to modify load binding for wireless switches, Wattstopper recommends using the DLM Config App for ease of use and available features. Load Selection Procedure In situations in which there is more than one load in a room, the configuration button allows access to Push n’ Learn technology to change the binding relationship between control devices and loads.
  • Page 6 The Apple logo, iPhone, iPod touch, and iTunes are trademarks © Copyright 2021 Tous droits réservés Legrand. Google Play and the Google Play www.legrand.us/wattstopper of Apple Inc., registered in the U.S. and other countries. © Copyright 2021 Legrand Todos los derechos reservados. logo are trademarks of Google Inc.