Do not select the sites that are not recommended by industry standards and
regulations, including but not limited to the following areas:
Issue 15 (2023-11-01)
It is recommended that outdoor open electrochemical energy storage plants
be equipped with fences and walls. The external walls of an electrochemical
energy storage plant deployed in a power plant or power transformation and
distribution station shall be permitted to serve as the enclosure and isolation
walls.
The safety distances between the ESS and buildings shall comply with local
fire protection regulations or standards.
The ESS and the site must be in an environment free from explosion risks.
Transportation to the site shall be convenient and fire suppression facilities
shall be reliable.
NO TE
● When installing, commissioning, and operating the ESS, ensure that at least two
gas fire extinguishers are provided near each unit to ensure fire safety.
● The distance between the exhaust device of an ESS and the heating and ventilation
vents, air intake vents of air conditioners, windows, doors, unloading platforms,
and fire sources of other buildings or facilities must be greater than 4.6 m.
● Reserve sockets for the water fire suppression system at the ESS site.
● Outdoor fire hydrants shall be installed around the plant. The distance between
fire hydrants shall be less than or equal to 60 m. The number of outdoor fire
hydrants shall be calculated based on the flow rate and protection radius of fire
hydrants. The maximum protection radius shall be less than or equal to 150 m, and
the flow rate shall be greater than or equal to 15 L/s.
The site area must meet the requirements and there shall be space for
capacity expansion.
The site shall be in a well-ventilated place.
The ESS shall not be installed in salt-affected or polluted areas because this
will cause corrosion. The ESS shall be used in the following or better
environments:
Outdoor environment more than 2000 m away from the coast. You are
advised not to use the ESS in an area 500 m to 2000 m away from the
coast. (If you need to use it, confirm with the vendor or the Company's
engineers.) Do not use the ESS in an area less than 500 m away from the
coast.
More than 1500–3000 m away from heavy pollution sources such as
smelteries, coal mines, and thermal power plants
More than 1000–2000 m away from medium pollution sources such as
chemical, rubber, and electroplating industries
More than 500–1000 m away from light pollution sources such as
packing houses, tanneries, boiler rooms, slaughterhouses, landfill sites,
and sewage treatment plants
NO TE
You are advised to select another site if the safety distance for a site cannot meet the
requirements of relevant national standards.
Areas with sources of strong vibration, loud noises, and strong
electromagnetic interference