Heating/cooling circuit distributor with mixer
Table of Contents

Advertisement

Extension kit with mixer PCB
Connecting the 24 V contact
humidistat directly to the heat pump
Depending on the heat pump type and
system equipment, 1 to 2 contact
humidistats can be connected directly
to the heat pump:

Rotary switch S1

(cont.)
Heat pump installation and serv-
ice instructions
If several mixer extension kits are being
connected, set rotary switch S1.
Set the rotary switch on each extension
kit to a consecutive number:
■ Heating/cooling circuit with mixer M2:
Rotary switch to 1
■ Heating/cooling circuit with mixer M3:
Rotary switch to 2
■ Heating/cooling circuit with mixer M4:
Rotary switch to 3
Note
If additional EM-P1 extensions are con-
nected, always set the subscriber num-
bers for the EM-P1 extensions to con-
secutive numbers after the mixer exten-
sion kits.
Note
On heat pumps: The cooling circuits
are assigned via the programming unit
or through the ViGuide service app.
23