Connecting The Temperature Limiter To Restrict The Maximum Temperature (Accessories) - Viessmann Divicon Installation Instructions Manual

Heating/cooling circuit distributor with mixer
Table of Contents

Advertisement

Extension kit with mixer PCB
Connecting the temperature limiter to restrict the maximum
temperature (accessories)
C
B
A
A Heating circuit pump
B Temperature limiter
C Plug sÖ to mixer extension kit
M
1~
(cont.)
Electromechanical temperature limiter
using the liquid expansion principle
■ Switches off the heating circuit pump
if the set value is exceeded.
■ The flow temperature is only slowly
reduced in this situation. It may take
several hours before the system
restarts again automatically.
■ Connection: Screw terminals for
2
1.5 mm
Specification
Setting range
Switching differential
■ Immersion thermostat
■ Contact thermostat
30 to 80 °C
Max. 11 K
Max. 14 K
21