Mode 1
Mode 1 is used to set basic settings and to monitor the
status of the unit.
Changing and access the setting in mode 1:
Once mode 1 is selected (push BS1 1 time), you can
select the wanted setting. It is done by pushing BS2.
Accessing the selected setting's value is done by
pushing BS3 1 time.
To quit and return to the initial status, press BS1.
Examples:
Checking the content of parameter [1-10] (to know how
many indoor units are connected to the system).
[A-B]=C in this case defined as: A=1; B=10; C=the value
we want to know/monitor:
Make sure the 7-segment indication is as during
normal operation (default situation when shipped
from factory).
Push BS1 1 time; result 7-segment display:
Result: mode 1 is accessed.
Push BS2 10 times; result 7-segment display:
Result: mode 1 setting 10 is addressed.
Push BS3 1 time; the value which is returned
(depending on the actual field situation), is the amount
of indoor units which are connected to the system.
Result: mode 1 setting 10 is addressed and selected,
return value is monitored information
To leave the monitoring function, push BS1 1 time,
you will return to the default situation when shipped
from factory.
Mode 2
Mode 2 is used to set field settings of the outdoor unit
and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (push BS1 for more than
5 seconds), you can select the wanted setting.
It is done by pushing BS2. Accessing the selected
setting's value is done by pushing BS3 1 time.
To quit and return to the initial status, press BS1.
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (push BS1 for more than
5 seconds) you can select the wanted setting.
It is done by pushing BS2.
- Accessing the selected setting's value is done by
pushing BS3 1 time.
- Now BS2 is used to select the required value of the
selected setting.
- When the required value is selected, you can define
the change of value by pushing BS3 1 time.
- Press BS3 again to start operation according to the
chosen value.
40
01_EN_3P748230-1.indd 40
Examples:
Checking the content of parameter [2-18] (to define the
high static pressure setting of the outdoor unit's fan).
[A-B]=C in this case defined as: A=2; B=18; C=the value
we want to know/change
Make sure the 7-segment indication is as during
normal operation (default situation when shipped
from factory).
Push BS1 for over 5 seconds; result 7-segment display:
Result: mode 2 is accessed.
Push BS2 18 times; result 7-segment display:
Result: mode 2 setting 18 is addressed.
Push BS3 1 time; the value which is returned
(depending on the actual field situation), is the status
of the setting. In the case of [2-18], default value is
"0", which means the function is not active.
Result: mode 2 setting 18 is addressed and selected,
return value is the current setting situation.
To change the value of the setting, push BS2 till the
required value appears on the 7-segment indication.
When achieved, define the setting value by pushing
BS3 1 time. To start operation according to the
chosen setting, confirm again by pushing BS3.
To leave the monitoring function, push BS1 1 time,
you will return to the default situation when shipped
from factory.
13.2.2 Operating the DIP switches
By operating the DIP switches it is possible to:
What to do with DIP switch DS1
NOT USED
2-4
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2
NOT USED
1-4
DO NOT CHANGE THE FACTORY SETTING