Daikin RXYQ6BRY16 Installation Manual page 53

Vrv system air conditioner
Table of Contents

Advertisement

[2-27]=
Low noise operation stop time.
Default value=3.
Value [2-27]
1
2
3
This setting is used in conjunction with
setting [2-22].
[2-30]=
Power consumption limitation level (step 1)
via the external control adapter (DTA104A62).
If the system needs to be running under
power consumption limitation conditions when
an external signal is sent to the unit, this
setting defines the level power consumption
limitation that will be applied for step 1.
The level is according to the table.
Default value=3.
Change [2-30]=1, 2, 3, 4, 5, 6, 7 or 8 in
function of required limitation.
Value [2-30]
1
2
3
4
5
6
7
8
[2-31]=
Power consumption limitation level
(step 2) via the external control adapter
(DTA104A62).
If the system needs to be running under
power consumption limitation conditions when
an external signal is sent to the unit, this
setting defines the level power consumption
limitation that will be applied for step 2.
The level is according to the table.
Default value=1.
Change [2-31]=1, 2 or 3 in function of
required limitation.
Value [2-31]
1
2
3
01_EN_3P748230-1.indd 51
[2-32]=
Stop time automatic low
noise operation
(approximately)
6:00
7:00
8:00 (default)
[2-34]=
Power consumption
limitation
(approximately)
60%
65%
70% (default)
75%
80%
85%
90%
95%
[2-49]=
Power consumption
limitation
(approximately)
40% (default)
50%
55%
Forced, all time, power consumption limitation
operation (no external control adapter is required
to perform power consumption limitation).
If the system always needs to be running
under power consumption limitation
conditions, this setting activates and defines
the level power consumption limitation that
will be applied continuously.
The level is according to the table.
Default value=0 (OFF).
Value [2-32]
Restriction reference
0
Function not active (default)
1
Follows [2-30] setting
2
Follows [2-31] setting
Change [2-32]=0, 1 or 2 in function of
required limitation.
Indoor unit fan tap setting.
Indoor units fan speed limitation related to
connection capacity and outdoor air
temperature for energy saving.
Default value=0.
Value [2-34]
Indoor unit fan tap setting
Fan speed is limited to L tap when
0
indoor units capacity ≥130%. (default)
In heating mode, fan speed is limited
1
to L tap when indoor units capacity
≥130%.
Fan speed follows the setting of remote
2
controllers (not limited by indoor units
connection capacity).
See the service manual for other indoor unit
fan tap settings.
Height difference setting.
Default value=0.
In case the outdoor unit is installed in the
highest position (indoor units are installed on
a lower position than outdoor units) and the
height difference between the lowest indoor
unit and the outdoor unit exceeds 50 m, the
setting [2-49] has to be changed follow below.
Value [2-49]
Height difference
0
≤50 m (default)
1
2
3
Other changes/limitations to the circuit apply,
for more information see "9.4 System piping
(length) limitations".
* T he setting [2-49] has to be changed to 1 if
not sure about the height difference between
the lowest indoor unit and the outdoor unit.
NOTICE
The maximum height difference setting will be
effect to performance of system decrease.
≤110 m
≤90 m
≤70 m
51