Multi-purpose monitor with high / low alarms, analog and pulse outputs, signal input sensor: 0 4-20 ma, signal outputs: 0 4-20 ma / 0-10 v ref. sensor signal or percentage, alarm outputs: maximum four level alarms, options: intrinsically safe, modbus comm (64 pages)
Batch controller with two-stage control, analog and pulse outputs signal input flowmeter: pulse, namur and coil external controls: start and stop digital outputs: two control outputs for two stage control, or one control output and pulse output ref. total (53 pages)
Page 1
F193-X MODBUS SLAVE DISPLAY Signal input: Modbus RTU / ASCII Signal outputs: 4-20mA and switch outputs Option: Intrinsically Safe F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
Compatibility). Do connect a proper grounding to the aluminum casing as indicated if the F193-X has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F193-X is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 Introduction ..........................5 1.1. System description of the F193-X ..................5 Operational ..........................7 2.1. General ..........................7 2.2. Control panel .......................... 7 2.3.
SYSTEM DESCRIPTION OF THE F193-X Functions and features The Modbus slave display model F193-X is a microprocessor driven instrument designed as local Modbus display with outputs which are controlled though communications as well. In total nine different product values can be displayed, maximum four alarm switch outputs and one analog output can be controlled.
Page 6
Page 6 Configuration of the unit The F193-X is designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F193-X according to your specific requirements. SETUP includes several important features, such as communication speed, address, measurement units etc.
Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F193-X. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
2.3. OPERATOR INFORMATION AND FUNCTIONS In general, the F193-X will always act at Operator level. The information displayed is dependant up on the SETUP-settings. The screen refresh rate setting might be slow but after pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
Operating Manual before carrying out its instructions. The F193-X may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 10
Page 10 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the function.
Page 11
Page 11 To change or a select a value or value: To change a value, use to select the digits and to increase that value. To select a setting, both and can be used. When the new value is not valid, the increase sign or decrease-sign will be displayed while you are programming.
Page 13 3.2.3. EXPLANATION SETUP-FUNCTIONS All functions described below can be read and modified through communication. However, it is also desired for the initial setup and for safety reason that all settings and data can be modified manually. The functions below do offer all these settings and data. 1 - CONFIGURE Do select the number of products to be available for the operator: PRODUCTS...
Page 14 2 - UNIT SETUP 21-29 determines for product 1 up to and including product 9 the MEASUREMENT UNIT displayed measurement unit. PRODUCT X 21 - 29 The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). 1 byte 0x0604 product 1 1=m3...
Page 15 5 - VALUE SETUP 51-59 determines for product 1 up to and including product 9 the VALUE DISPLAYED displayed value. The minimum value is 0 and the maximum value is PRODUCT X seven digits. 51 - 59 3 bytes 0x0600 product 1 0.000 ...
When used with the internal battery option type PB / PC, the user may hold the concern of reliable display over a long period of time. The F193-X has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
Page 17
Page 17 The initial minimum analog output value is 0/4mA or 0V. However, this TUNE MIN / 4MA value might differ slightly due to external influences such as temperature for example. The 0/4mA or 0V value can be tuned precisely with this setting.
1…9,999 B - OTHERS For support and maintenance it is important to have information about the TYPE OF MODEL characteristics of the F193-X. Your supplier will ask for this information in the case of a serious breakdown. 0x0001 2 bytes...
Page 19 3.2.4. ADDITIONAL COMMUNICATION FUNCTIONS PRODUCT DISPLAYED This register determines the product currently displayed. 0x060F 2 bytes 0=product 1 1=product 2 2=product 3 3=product 4 4=product 5 5=product 6 6=product 7 7=product 8 8=product 9 This register contains a bitfield with the packed variable data of registers ALARM STATUS 0x0607 ...
Personnel must read and understand this Operating Manual before carrying out its instructions. The F193-X may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ...
Do ground the aluminum enclosure properly as indicated, if the F193-X has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
TYPE OA / TYPE PD / PF / PM OT / OR OT / OR AI / AP / AU OT / OR Fig. 7: Overview of terminal connectors standard configuration F193-X and options. POWER SUPPLY ANALOG ALARM ALARM ALARM...
Page 25
Page 25 REMARKS: TERMINAL CONNECTORS: Terminal GND- 01- 02 only available with type PD / PF or PM: erminal SENSOR SUPPLY PD 8-24V AC Not available ◊ ◊ ◊ ◊ PD 8-30V DC Not available ◊ ◊ ◊ ◊ PF 24V AC ± 15% Not available ◊...
Page 26
Page 26 Type OR: A mechanical relay output is available with this option. Max. switch power 240V 0,5A per output. (Requires power supply type PF / PM). Type OT: A passive transistor output is available with this option. Max. driving capacity 300mA - 50V DC per output. HF193XEN_v0501_04...
Page 27
Page 27 Terminal 07-08; basic POWER SUPPLY - type PX - output loop powered: Connect an external power supply of 8-30VDC to these terminals or a 4-20mA loop. Do connect the "-" to terminal 7 and the "+" to terminal 8. When power is applied to these terminals, the (optional) internal battery will be disabled / enabled automatically to extend the battery life time.
Page 28
Page 28 Type AP: A passive 4-20mA signal proportional is available with this option. When a power supply is connected but the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm. This output does loop power the unit as well (type PX). Type AU: A 0-10VDC signal is available with this option.
Page 29
Page 29 Terminal 26-31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL (option) Full serial communications and computer control in accordance with RS232 (length of cable max. 15 meters) or RS485 (length of cable max. 1200 meters) is possible. Read the Modbus communication protocol and Appendix C.
Please Note Certificates, safety values and declaration of compliance can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”. Special conditions for safe use mentioned in both the certificate and the installation instructions must be observed for the connection of power to both input and / or output circuits.
Indicated labels on the back cover (below) and on the inside cover (right) show the type labels for intrinsically safe certified units. For details on usage see the separate “Fluidwell F1..-..-XI Documentation for Intrinsic Safety”. Serial number and year of production This information can be looked-up on the display: See setup function (par.
Page 32
Page 32 Explanation Intrinsically Safe options: Type AF - Intrinsically Safe floating 4-20mA analog output: A floating 4-20mA signal with this option. When the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm @ 30V DC. Type PD - Intrinsically Safe power supply and sensor supply - Terminal GND- 01 and 11.
Page 33 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS Configuration example IIB /IIIC F193-X-AP-CT-OT-PD-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL ISOLATOR: Uo=30V I.S. Certified Isolator e.g. PC TTL to Io=250mA RS232 / RS422 / TTL...
Page 34
Page 34 Configuration example IIB /IIIC F193-X-AP-CT-OT-PD-XI HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100-series Modbus communication type CT: TTL Please note: communciation type CT is allowed in IIC applications. ISOLATOR: Uo=30V I.S. Certified Isolator e.g. PC TTL to Io=250mA...
Batteries for use in safe areas have no Ex label. DO NOT EXCHANGE: Using the wrong type of battery can pose a SERIOUS RISK. For use in hazardous areas Fluidwell recommends FW-LiBAT batteries (manufactured by Fluidwell bv) only. Battery replacement procedure Depending on the production batch, one of two visualized Intrinsically Safe certified battery types may have been installed in the unit.
Operating Manual before carrying out its instructions. The F193-X may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 37 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec _ 30 secs. Option ZB Transflective LCD with green LED backlight.
Page 38
Page 38 Hazardous area (option) Intrinsically safe ATEX approval ref: <EX> II 1 GD EEx ia IIB/IIC T4 – T100°C. Type XI Explosion proof ATEX approval ref.: <EX> II 2 GD EEx d IIB T5. Weight appr. 15kg. Type XD/XF Dimensions of enclosure: 350 x 250 x 200mm (13.7”...
Page 39 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F193-X is going to be installed or while it is in operation. Analog output does not function properly: Check: SETUP 91 - is the function enabled? ...