LIGHT OIL TUBING INSTALLATION DIAGRAM
FROM TANK
TO TANK
Key
1 Burner
2 Flexible hoses (supplied)
3 Light oil filter (supplied)
4 Automatic interception device
5 One-way valve
6 Gate valve
7 Quick-closing gate valve (not in the same room as tank or boiler)
Determining diameter of light oil supply pipes
Tab. 1
L (m)
H
(m)
Ø 6
Ø 8
Ø 10
0
41
100
100
0.5
70
100
100
1
100
100
100
1.5
100
100
100
2
100
100
100
2.5
100
100
100
3
100
100
100
3.5
100
100
100
4
100
100
100
4.5
100
100
100
5
100
100
100
Single pipe system
The burners leave the factory ready for a 2 pipes supply system.
It is however possible to transform them for a single pipe supply system (advisable in the case of a gravity feed system).
See appendix for details of the operations to be carried out.
Fig. 6
Fig. 7
Tab. 2
L (m)
H
(m)
Ø 6
Ø 8
Ø 10
0
19
77
100
1
24
90
100
2
30
100
100
3
34
100
100
4
39
100
100
5
44
100
100
6
48
100
100
7
52
100
100
8
56
100
100
9
55
100
100
10
51
100
100
PART I: INSTALLATION MANUAL
H
(m)
Ø 12
100
0
100
0.5
100
1
100
1.5
100
2
100
2.5
100
2.5
100
3
100
3.5
100
4
100
4.5
Tab. 3
L (m)
Ø 6
Ø 8
Ø 10
Ø 12
18
73
100
100
15
66
100
100
13
59
100
100
10
52
100
100
7
44
100
100
5
44
100
100
-
37
100
100
-
30
85
100
-
23
68
100
-
-
-
100
-
-
-
-
7