Siemens SIMATIC S7-1500 System Manual page 423

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Commissioning
12.6 Backing up and restoring the CPU configuration
Entries in the diagnostics buffer
Current time
Password for protection of confi-
dential configuration data
Backup can be edited
Backup possible in system state
From backup CPU
1)
Example: Backup from online device
The following example shows how to carry out a complete backup of the current device state
of the CPUs in STEP 7. The S7-1500R/H redundant system is in the RUN-Redundant system
state. Special consideration should be given to the following:
• Before the backup, the backup CPU goes into STOP mode.
• The CPU data of the backup CPU is backed up.
To start the backup, proceed as follows:
1. Right-click to select the S7-1500R/H system in the project tree.
2. Select the "Backup from online device" command from the shortcut menu.
3. The "Upload preview" dialog window sets out the key information on the backup process to
be run. To make a backup, you need to set the S7-1500R/H redundant system to the RUN-
Solo system state.
Note: If you open the entry "Stop module" in the preview, then you can see which CPU is
stopped.
4. In the "Action" column, select the "Stop module" command from the drop-down menu.
5. Click "Upload from device". The backup CPU switches to the STOP operating state. The
backup of the CPU data of the backup CPU begins. The backup is saved in the folder of the
top CPU in the project tree.
6. Switch the redundant system to the RUN-Redundant system state again.
Example: Restoring a backup of an online device
If you have saved the CPU data beforehand, you can transfer the backup back to the device.
The saved backup is then restored to the CPU.
The S7-1500R/H redundant system is in the RUN-Redundant system state. Special
consideration should be given to the following:
• The backup is loaded into the primary CPU.
• Before the restore, the redundant system goes to the STOP system state.
422
Backup from
Upload from de-
online device
vice (software)
--
--
--
Properties of the type of backup
--
RUN-Solo
, STOP
RUN-Redundant,
1)
RUN-Solo, STOP
Upload device as
new station
--
--
--
--
--
--
RUN-Redundant,
RUN-Solo, STOP
System Manual, 01/2024, A5E41814787-AF
Snapshot of the
actual values
--
--
--
RUN-Redundant,
RUN-Solo, STOP
S7-1500R/H redundant system