Siemens SIMATIC S7-1500 System Manual page 283

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Wiring
8.9 Connecting interfaces for communication with S7-1500H
3. Hold the pre-assembled connectors of the redundancy connection by the housing. Push the
connectors into the sockets of the synchronization modules. You should hear the
connectors click into place.
4. Repeat steps 1 to 3 for the second H-CPU.
Figure 8-12
Uninstalling a synchronization submodule
To uninstall the synchronization modules, follow these steps:
1. Press down lightly on the connector release and hold while pulling the connector out of the
synchronization module.
2. Flip the synchronization module clip to the right.
3. Pull the synchronization module out of the H-Sync interface on the CPU.
4. Place the blanking plug on the synchronization module.
5. Repeat the process for all H-Sync interfaces on the H-CPUs.
282
Connecting redundancy connections (fiber-optic cables) to S7-1500H
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents