Application planning
6.1 Requirements
Property
PROFINET devices
130
Requirement
Media redundancy (MRP)
All PROFINET devices in the PROFINET ring support the function media redundancy.
Both CPUs have the media redundancy role "Manager (auto)". All other devices in the
PROFINET ring have the media redundancy role "Client".
H-Sync forwarding
- for PROFINET devices in the PROFINET ring with S7-1500R:
2)
When you use PROFINET devices with more than two ports (e.g. switch) in the
PROFINET ring of an R-system, then H-Sync forwarding is mandatory for these devices.
H-Sync forwarding is recommended for all devices in the PROFINET ring if you are us-
ing PROFINET devices with only 2 ports in the PROFINET ring of an R-system.
Redundancy:
With the switched S1 device function, you can operate any standard IO device on the
redundant S7-1500R/H system.
An IO device must support system redundancy S2 or R1 for uninterrupted exchange
of process data in the event of failure of the primary CPU (primary-backup switch-
over).
The following SIMATIC PROFINET IO devices support system redundancy S2, media redun-
dancy and H-Sync forwarding:
ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0), FW version V4.2 or higher
ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0), FW version V4.2 or higher
ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0), FW version V4.2 or higher
ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), FW version V5.0.1 or higher
ET 200MP (6ES7155-5AA00-0AC0), FW version V4.2 or higher
PN/PN coupler (6ES7158-3AD10-0XA0), FW version V4.2 or higher
PN/MF coupler (6ES7158-3MU10-0XA0), FW version V5.0 or higher
IE/PB LINK HA (6GK1 411-5BB00), FW version V4.1 or higher
The following SIMATIC PROFINET IO devices support system redundancy R1, media re-
dundancy:
ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0), FW version V6.0 or higher. A list
of compatible I/O modules for the IM 155-6 PN R1 interface module can be found in
the Product information for the documentation of the ET 200SP
(https://support.industry.siemens.com/cs/en/en/view/73021864) distributed I/O sys-
tem. The R1 capability is also specified in the technical specifications of the I/O mod-
ules.
ET 200SP HA IM 155-6 PN HA (6DL1155-6AU00-0PM0), FW version V1.2 or higher
ET 200iSP IM 152-1 PN for ET200iSP for standard and redundant operation (6ES7152-
1BA00-0AB0), FW version V1.0 or higher
The following switch product families support system redundancy S2, media redundancy,
and H-Sync forwarding:
XC-200, XP-200 and XF-200BA, e.g. SCALANCE XC208 (6GK5208-0BA00-2AC2), FW
version V4.0 or higher
XM-400 and XR-500, FW version V6.3.0 or higher
S7-1500 CPUs: As of firmware version V2.5
When determining the maximum number of IO devices inside and outside the PROFINET
ring, the redundant system in STEP 7 does not recognize the S7-1500 CPUs. If you use S7-
1500 CPUs, you will have to check the maximum number yourself.
SINAMICS S120 PROFINET Control Unit (CU310-2 PN or CU320-2 PN) supports system
redundancy S2, media redundancy and H-Sync forwarding as of FW version V5.2.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF