¢ Models: AOUH24LUAS1, AOUH30LUAS1, and AOUH36LUAS1
The minimum rotation number of compressor is limited by outdoor temperature as below.
• Cooling/Dry mode
Model name
AOUH24LUAS1
AOUH30LUAS1
AOUH36LUAS1
1-5. Rotation number of compressor limitation by outdoor temperature
H zone
125.6°F
(52°C)
G zone
122.0°F
(50°C)
F zone
107.6°F
(42°C)
E zone
100.4°F
(38°C)
D zone
69.8°F
(21°C)
C zone
55.4°F
(13°C)
B zone
44.6°F
(7°C)
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
- (04-9) -
Unit: rps
Limitation of compressor
frequency
29
29
29
24
19
21
28
32
30
26
20
20
15
24
27
35