1-2. Heating operation

A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 11°F (6.0°C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
• If the room temperature is 2°F (1.0°C) higher than a set temperature, the compressor will be
stopped.
• →hen the room temperature is within the range of +2°F (1.0°C) to -11°F (6.0°C) of the setting tem-
perature, the rotation number of compressor is controlled within the range shown below.
• Rotation number range of compressor
Model name
AUUH18LUAS
AUUH24LUAS
AUUH30LUAS
AUUH36LUAS
1-2. Heating operation
Minimum frequency
8
10
15
15
- (04-3) -
Unit: rps
Maximum frequency
130
130
110
120
1. Rotation number control of compressor