7-13. Peak cut operation (for 24/30/36 model)

The current value is limited to reduce the power consumption by external input.
Peak cut level
Peak cut for rated capacity
NOTES:
• During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.

7-14. Unit status monitoring and the detected value indication

The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of "Display Sensor Values" in the Installation
Manual of →ired Remote Controller (Touch Panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE: Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Sensor ID
00: Indoor unit
00
000
Suction temp.
00
001
Room temp.
→ired remote controller detected
00
002
temp.
00
006
Heat exchanger middle temp.
00
020
Fan rotation number
00
021
Fan 2 rotation number
00
051
Float switch On/Off
00
052
Drain pump On/Off
00
080
Indoor unit total energized hours
00
081
Total filtering hours
00
082
Indoor unit fan total operation hours
00
083
Indoor unit fan 2 total operation hours
Presence or absence detected by
00
095
human sensor
00
140
Operation or Stop (External input)
7-13. Peak cut operation (for 24/30/36 model)
Level 1
Forced thermostat
off
Available Sensor ID
Item
01: °F or °C
01: °F or °C
01: °F or °C
01: °F or °C
- (04-35) -
Level 2
Level 3
50%
75%
Unit
→hen the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
03: rpm
03: rpm
0: Off, 1: On (→hen the water level
08: On/Off
rises)
08: On/Off
0: Off, 1: On
11: h
11: h
11: h
11: h
0: Absence, 1: Presence
00: —
—: Human sensor error or No human
sensor
0: Off, 1: On
—: →hen the function setting 46 is
not set
00: —
NOTE: Available only for external
input port of the indoor unit
Level 4
100%
Remarks
7. Various control