Fujitsu AUUH18LUAS Service Manual page 180

Cassette type
Table of Contents

Advertisement

¢ Models: AOUH24LUAS1, AOUH30LUAS1, and AOUH36LUAS1
The compressor is controlled as follows.
• Cooling mode
Indoor unit heat exchanger
temperature rises
AB
BC
Zone C
Zone
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
Zone C
The protection is released and the operation is returned to normal mode.
Zone D
• Heating mode
Indoor unit heat exchanger
temperature rises
AB
BC
CD
Zone D
Zone
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
Zone C
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-8. High temperature and high pressure release control
Indoor unit heat exchanger
temperature drops
Zone A
Zone B
Stable zone
CD
Zone D
Indoor unit heat exchanger
temperature drops
Zone A
Zone B
Zone C
Stable zone
DE
Zone E
- (04-42) -
AB:
149.0°F (65°C)
BC:
143.6°F (62°C)
CD:
140.0°F (60°C)
Operation
AB:
145.4°F (63°C)
BC:
131.0°F (55°C)
CD:
127.4°F (53°C)
DE:
122.0°F (50°C)
Operation
-7 rps/120 sec.
-15 rps/120 sec.
-2 rps/120 sec.
8. Various protections