2-3. E: 12. Wired remote controller communication error (Indoor
unit)
→ired remote
Indicator
controller
Indoor unit
Detective actuator
→ired remote control
Forecast of cause
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 1-2 : Check →ired remote controller
and main PCB
Check voltage at CN14 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
Check Point 2 : →ire installation wrong remote controller group setting
→rong wire connection in remote controller group (Please refer to the installation manual)
The number of connecting indoor unit and remote controller in one remote controller group
were less than 32 units.
Check Point 2-1 : Check Indoor unit main PCB
Check if main PCB damage
Change main PCB and check the error after setting remote controller address
2-3. E: 12. →ired remote controller communication error (Indoor unit)
Error code
Main PCB
End
End
→hen the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
3-wire type: 1 minute
2-wire type: 2.5 minutes
Terminal connection abnormal
→ired remote control failure
Main PCB failure
If it is DC 13 V, remote controller is failure.
(Main PCB is normal)
Replace remote control
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
Replace main PCB
- (03-9) -
E: 12