Fujitsu AUUH18LUAS Service Manual page 224

Cassette type
Table of Contents

Advertisement

 Auxiliary heat pump control by outdoor temperature 3
• External heater output
Operation
Heater on
Heater off
– Temperature of heater on (Thon): Set temperature (Ts) -0.9°F (-0.5°C)
– Temperature of heater off: Set temperature (Ts) +0.9°F (+0.5°C)
Tr-Ts ≥ 0.9°F
(0.5°C)
• Auxiliary heat pump On/Off
– Temperature of heat pump on (Thon): Adjustable by function number 62 (Operating temperature
switching of heat pump).
– All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ 0.9°F
(0.5°C)
*: →hen room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
• Outdoor temperature zone
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F (2°C): -0.4°F (-18°C)
*: Adjustable by function setting 66 and 67
3-5. Details of control output function
Heater is on as shown in following diagram of heating temperature.
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Tr-Ts
Off
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
On
Tr-Ts
Off
Tr-Ts (=Thon) < -0.9°F (-0.5°C)
On
Outdoor temp.
Heater only zone  
 
B: 42.8°F (6°C)*
Combination zone
  (Heat pump + Heater)
A: -4°F (-20°C)*
Heater only zone
 
Condition
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
*
Tr: Room temperature
Ts: Set temperature
Thon: Heat pump on temperature
 
 
- (05-42) -
3. External input and output (for indoor unit)