2-30. E: 95.X. Compressor motor control error (Outdoor unit)
→ired remote
Indicator
controller
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Check noise from compressor
Turn on power and check operation noise.
If an abnormal noise show, replace compres-
sor.
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open. (Refer to inverter compressor in
53.)
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace inverter PCB
If Check point 1, 2 do not improve the symptom, change inverter PCB.
Check point 4. Replace main PCB
If Check point 3 do not improve the symptom, change main PCB.
Check point 5. Replace compressor
If Check point 4 do not improve the symptom, change compressor.
2-30. E: 95.↓. Compressor motor control error (Outdoor unit)
Error code
Inverter PCB
Main PCB
Compressor
End
"Protection stop by "overcurrent generation at inverter
compressor starting" restart" generated consecutively 50
times x 3 sets (total 150 times) (for 18 model) or 10
times x 3 sets (total 30 times) (for 24/30/36 model).
Defective connection of electrical components
Inverter PCB failure
Main PCB failure
Compressor failure
"Service parts information"
- (03-36) -
E: 95
on page 03-
2. Troubleshooting with error code