Ecoflam OILFLAM 400.1 PR TL Manual page 19

Table of Contents

Advertisement

START-UP
Gefran setting
Display
Increase key
The display shows oil temperature.
The 4 leds are related to the following functions:
• Out 1: contact driving working heaters
• Out 2: contact driving upper heaters KMRL1
• Out 3: contact driving upper heaters KMRL2
• Out 4: burner start driving contact (as the oil reaches this temp the pump is activated)
The temperatures are already properly factory setted:
• Out 1 (113°)
• Out 2 (115°)
• Out 3 (120°)
• Out 4 (105°)
WARNING: Burner will start only when the first three led of the temperature will be off so that heavy oil will be in temperature.
To modify factory temperature setting act as follow:
• press key "F"
• the led Out 1 starts to ash, if You need to modify minimum oil temperature press increase or decrease button, after confirm the new
value pressing again "F"
• if you need to modify an other temperature press again "F" untill You the relevant led ashes.
Please take care: if key "F" is pressed for a too long time, you enter in "configuration level" phase 1, (see "CF1" on the display);
these parameters are factory setted and they have not to be modified: if you enter this function – you see CF1 ashing on the display –
wait 10 seconds until the regulator automatically goes out from "configuration level".
420010466301
ADJUSTMENT OF FUEL THERMOSTATS
Inside the electrical panel there is a safety termostat
that is set up at 160°C.
Said adjustments can be slightly modified following
the type of fuel and particular uses.
Decrease key
"Function" key