The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
UPS output receptacles. WARNING! Do not modify the cables in any way. Consult your local Vertiv representative, if the AC cords do not match the MAINS receptacle. The Liebert® MicroPOD must be grounded at all times while in use. Turn Off the UPS before unplugging Liebert®...
Vertiv™ Liebert® MicroPOD Installer/User Guide 2 Introduction and System Description The Vertiv™ Liebert® MicroPOD provides maintenance bypass capability as well as power output distribution. The Liebert® MicroPOD can be used on UPSs in either rack mount or tower configuration. The Liebert® MicroPOD provides an isolated path of power for your UPS system for preventive maintenance or service.
3 Installation 3.1 Installation on the Vertiv™ Liebert® Rack UPS NOTE: This manual provides instructions for the Vertiv™ Liebert® MicroPOD only. Refer to your UPS manual for related operation and installation instructions. Unpack the Liebert® MicroPOD carefully, noting the packaging method. Retain the box and packaging material for possible future shipments.
Vertiv™ Liebert® MicroPOD Installer/User Guide 3.2 Rack Mount Installation Rack mount installation of the Vertiv™ Liebert® MicroPOD is possible with the use of the rack mounting brackets (shipped with the Liebert® MicroPOD). See Figure 3.2 below. 2. The rack mount brackets allow you to rack mount the Liebert® MicroPOD in a 19 in. enclosure.
CAUTION: The MAINS input supply to the Vertiv™ Liebert® MicroPOD must be protected by a branch rated circuit breaker. The UPS output must also be protected with a circuit breaker connected to the load, rated to carry the input current and be capable of breaking the maximum expected short circuit current of this branch circuit.
This green lamp is illuminated when output power is available from the UPS, see Figure 5.1 below. It signals that it is safe to transfer connected loads from MAINS power back to UPS output power. Figure 5.1 Indicator Lamps on Vertiv™ Liebert® MicroPOD Item...
Ensure the MAINS lamp (amber) is illuminated. If the lamp is not illuminated, refer to Troubleshooting on page 15. 2. Transfer the rotary switch from UPS to MAINS, provided the MAINS lamp is illuminated on the Vertiv™ Liebert® MicroPOD. 3. Turn the UPS off.
Page 18
The UPS input cord is compatible with the rating and type of receptacle on the Liebert® MicroPOD labeled CONNECT UPS LINE CORD HERE. • The UPS output cord is compatible with the rating and type of receptacle on the Vertiv™ Liebert® MicroPOD labeled UPS. •...
Refer to Liebert® MicroPOD installation instructions in this manual: MAINS lamp (amber) not illuminated Vertiv™ Liebert® MicroPOD input cord • Installation on the Vertiv™ Liebert® Rack UPS on page 5 not connected to MAINS • Rack Mount Installation on page 6 Turn on the UPS.