4.7.3 Emptying Mode
Function Switch Setting
Fig 21: Emptying Mode Setting and Display
Operation:
Normal liquid level in the sump
Fig 22 When the water level reaches Probe 3 (Float Switch A: Up Level), the controller
will run a single pump; when the water level declines to Probe 2 (Float Switch A: Down
Level), the single pump stops running.
When the water level varies from Probe 2 & Probe 3 (Float Switch A: Up level Down
level), the controller will alternate the two pumps automatically.
Excess Flow into the Sump
When the water level in the sump rises to Probe 4 (Float Switch B: Up level), and a single
pump is running, the controller will run the second pump to drain the water till the level
declines to Probe 2 (Float Switch A & B: Down Level), then both pumps stop running.
Overow in the sump
When the water level in the sump rises to Probe 5 (Float Switch C: Up level), the
controller will sound a warning alarm and run both pumps simultaneously. When water
level declines to Probe 5 (Float Switch C Down Level), the controller stops sounding
warning alarm.
Fig 22: Emptying Mode with Level Electrodes at Source Tank