DAYLIFF SMARTCON 2 Installation & Operating Manual page 12

Intelligent pump controller

Advertisement

4.4 Installation of Water level Electrode Probe & Float Switch
Signal Cable
Installation
Stand
Fig 7: Water Level Electrode (Probe)
Installation
In event of high risk of electric storms (lightning) or when
liquid medium in well or tank or sump is very dirty it is
recommended that a oat switch is used.
CAUTION
If the oat switch has three wires, use Black and Brown wires.
If the oat switch has different colors, use a multimeter to
identify connections as follows: Low Level - no reading [OFF],
CAUTION
High Level - positive reading [ON]
Do not enclose sensor leads, oat switch wires or signal
cables within metal pipes, instead use PVC or PE tubing.
CAUTION
4.5 Installation of Temperature Sensor
To connect the temperature sensor, the motor must have a thermal switch embedded in
the motor windings. Connect the thermal switch with the NC (normally closed) contact.
If the motor doesn't have a thermal switch, the terminals 9, 10 and 10, 12 should be
connected using two jumpers.
Fig 9: Temperature Sensor Connection
Wrap the signal cable
and down-lead of sensor
Fixation cone
Down-lead
of sensor
Upper
Probe
Lower Probe
Com Probe
Fig 8: Float Switch Installation
8
Upper Level (ON)
Lower Level (OFF)