4.5.3 Modbus Configuration Register Table Modbus Sensor

Setup/
Addr
Dir
Runtime
Setup
112
R/W
Setup
2000
R/W
Setup
2001
R/W
Setup
2002
R/W
Setup
2010
R/W
Setup
2011
R/W
Setup
2012
R/W
Setup
2013
R/W
Setup
2014
R/W
Setup
2015
R/W
Setup
2016
R/W
32
Non-
Name
Volatile
V
cfgHandling
Command
NV
cfgBaudrate
NV
cfgParity
NV
cfgStopBits
NV
cfgTempSensor
Offset
NV
cfgHumiSensor
Offset
NV
cfgCO
Sensor
2
Offset
NV
cfgPM2.5Sensor
Offset
NV
cfgTVOCSensor
Offset
NV
cfgPM1.0Sensor
Offset
NV
cfgPM10Sensor
Offset
Bits
SKU
Type/Unit
Num
3N/
int16
16
3D/
5N/5D
3N/
enum/
16
3D/
int16
5N/5D
3N/
enum/
16
3D/
int16
5N/5D
3N/
int16
16
3D/
5N/5D
3N/
signed/
16
3D/
int16
5N/5D
3N/
signed/
16
3D/
int16
5N/5D
3N/
signed/
16
3D/
int16
5N/5D
5N/5D
signed/
16
int16
5N/5D
signed/
16
int16
5N/5D
signed/
16
int16
5N/5D
signed/
16
int16
Range
0-3
0: 1200 baud
1: 2400 baud
2: 4800 baud
3: 9600 baud
4: 14400 baud
5: 19200 baud
6: 38400 baud
7: 57600 baud
8: 115200 baud
0: none
1: odd
2: even
1-2
o
-9 to 9(
F)
o
-5 to 5(
C)
-10 to 10
-1000 <=
cfgCO2SensorOffset <=
1000Tips of configuring
cfgCO2SensorOffset:
1. There must be an
interval of 3 minutes
between the two times
calibrations of CO2 written
into TR50, and less than
this interval writing
operation will cause failure.
2. TR50 can only accept the
CO2 sensor offset value
which meets requirement
that CO2 sensor reading +
offset value > 400 ppm
-
-
-
-
TR50 - User Guide
Default
0
5
2
1
0
0
0
0
0
0
0