Honeywell TR50 User Manual page 41

Indoor air quality sensor
Hide thumbs Also See for TR50:
Table of Contents

Advertisement

Setup/
Addr
Dir
Runtime
Setup
3022
R/W
Setup
3023
R/W
Setup
3030
R/W
Setup
3031
R/W
Setup
4000
R/W
Setup
4001
R/W
Setup
4004
R/W
Setup
4005
R/W
Setup
4020
R/W
Setup
5000
R/W
Setup
5001
R/W
Setup
5040
R/W
36
Non-
Name
Volatile
NV
cfgLcdParameter
Switch
NV
cfgLcdDimBright
ness
NV
cfgLedRingLcd
DimTime
NV
cfgLedRingLcd
TimeoutTime
NV
cfgTemperature
Unit
NV
cfgDisplayUnit
Temp
NV
cfgTVOCUnit
NV
cfgDisplayUnit
TVOC
NV
cfgLedRingLcd
Enable
NV
cfgModbusAuto
BaudrateEnable
V
cfgModbusFrame
CntClear
NV
cfgLocalDetection
Enable
Bits
SKU
Type/Unit
Num
3D/5D
enum/
16
int16
3D/5D
int16
16
3D/5D
int16
16
3D/5D
int16
16
3N/
bit/boolean 1
3D/
5N/5D
3D/5D
bit/boolean 1
5N/5D
bit/boolean 1
5D
bit/boolean 1
3N/
bit/boolean 1
3D/
5N/5D
3N/
bool
1
3D/
5N/5D
3N/
bool
1
3D/
5N/5D
3N/
bool
1
3D/
5N/5D
Range
For TR50-5D,
1: Auto cycling (default)
2: Manual + AQI (as the
static page)
3: Manual + Temperature
(as the static page)
4: Manual + Humidity (as
the static page)
5: Manual + CO2 (as the
static page)
6: Manual + PM2.5 (as the
static page)
7: Manual + TVOC (as the
static page)
8: Manual + no static page
For TR50-3D,
1: Auto cycling (default)
2: Manual + AQI (as the
static page)
3: Manual + Temperature
(as the static page)
4: Manual + Humidity (as
the static page)
5: Manual + CO2 (as the
static page)
6: Manual + no static page
10-40
3-10(s)
0(s), 10-30(s)
-Fahrenheit: 0
-Celsius: 1
-Fahrenheit: 0
-Celsius: 1
-ppb: 0
3
-ug/m
: 1
-ppb: 0
3
-ug/m
: 1
ON or OFF
TRUE or FALSE
TRUE or FALSE
TRUE or FALSE
TR50 - User Guide
Default
1
40
10s
0(s)
Fahrenheit
Fahrenheit
ppb
ppb
ON/1
TRUE
TRUE
TRUE

Advertisement

Table of Contents
loading

Table of Contents