PoolPak PCP-1200-NP-I-A2NT4172E1C4AN4 Manual

Omni-broomall pool

Advertisement

Project Name:
Prepared For:
PoolPak Model #: PCP-1200-NP-I-A2NT4172E1C4AN4
OACC Model #:
https://www.poolpak.com
3491 Industrial Drive
York, Pennsylvania 17402
1-717-757-2648
November 24, 2020
Omni - Broomall Pool
Sam Coniglio
Building Systems & Services
NC-B-1V-AUCSM-V

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PCP-1200-NP-I-A2NT4172E1C4AN4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PoolPak PCP-1200-NP-I-A2NT4172E1C4AN4

  • Page 1 Project Name: Omni - Broomall Pool Prepared For: Sam Coniglio Building Systems & Services PoolPak Model #: PCP-1200-NP-I-A2NT4172E1C4AN4 OACC Model #: NC-B-1V-AUCSM-V https://www.poolpak.com 3491 Industrial Drive York, Pennsylvania 17402 1-717-757-2648 November 24, 2020...
  • Page 2: Table Of Contents

    Table of Contents Unit Summary Design and Unit Performance Unit Dimension Drawing Condenser Dimension Drawing Features Summary Installation Field Wiring Diagram Remote Operator Panel General Specification Warranty Factory Assisted Start-Up Submittal 57106.1 Page 2 of 30 Nov 24, 2020...
  • Page 3: Unit Summary

    Unit Summary Omni - Broomall Pool PCP-1200-NP-I-A2NT4172E1C4AN4 Model 3 Ton compressor dehumidifier Unit Subseries No Pool Water Heater Unit Location Indoor Cabinet Compact (Small) Supply Voltage 208V/3PH Unit Control CommandPak c/w Remote Panel Refrigerant R410A Outdoor Air Duct Collar c/w Manual Damper & Filter...
  • Page 4: Design And Unit Performance

    Design and Unit Performance Omni - Broomall Pool PCP-1200-NP-I-A2NT4172E1C4AN4 Design Data Outdoor Air (CFM) 0.5 inches Room Conditions (°FDB/%RH) 82/60 Unit Total Airflow (CFM) 1750 Electrical Data Unit Voltage (V/Ph/Hz) 208V/3PH/60 Unit Full Load Amps - FLA (A) 101.0 Unit MCA (A) (min circuit ampacity)
  • Page 5 Design and Unit Performance Evaporator Coil Sensible Capacity (MBH) 22.8 Total Capacity (MBH) 40.7 Latent Capacity (Lbs/h) 16.2 Circuits Reheat Coil Total Heat Rejection (MBH) 50.9 Auxiliary Heat Location Unit Mounted Type Electric Heater Capacity (kW) 30.0 FLA (A) 83.3 Control 2 Stages Remote Outdoor Air-Cooled Condenser...
  • Page 6: Unit Dimension Drawing

    CAD FILE CAD FILE PPS0S-F4HCO-F5THT-F3LDP-0-0-0-SRE0 DATE DATE 2018-06-01 E.Hatin DRAWN BY DRAWN BY 1 of 2 SHEET SHEET 46.25 DESCRIPTION DESCRIPTION Cab S 17.5 19.75 * Refer To Unit Summary Sheet For Options Selected. Unit operating Weight: 450 LBS. 8.75 32.25 5.75 6.25...
  • Page 7 CAD FILE CAD FILE PPS0S-F4HCO-F5THT-F3LDP-0-0-0-SRE0 DATE DATE 2018-06-01 E.Hatin DRAWN BY DRAWN BY 2 of 2 SHEET SHEET *Heater Control Box DESCRIPTION DESCRIPTION Cab S Supply Air Outdoor *Electric Heater Return Air Supply Air Return Air Compressor Door Electrical Door *OA Damper Blower door Removable Legs...
  • Page 8: Condenser Dimension Drawing

    CAD FILE NC-B-1V rev03 Noise l e vel at 10' (may vary due to installation): DATE Low speed, 40 dBA 01/07/19 High speed, 50 dBA DRAWN BY SHEET dslater 1 OF 1 DESCRIPTION NC-B VERTICAL AIR FLOW, 1 CIRCUIT 30 1/2 33 1/4 36 5/8 Non-Fused Disconnect...
  • Page 9: Features Summary

    Features Summary VIRTUAL-TECH TECHNOLOGY – REMOTE INTERNET CONTROL, DIAGNOSTICS ® AND REPORTING There’s only one way we could provide superb, factory-engineered performance after a dehumidifier leaves our plant. It’s called Virtual-Tech Technology. Virtual-Tech Technology provides a powerful array of capabilities designed to ensure peak operating performance, a minimum of down time and the absolute lowest cost of ownership in the industry.
  • Page 10 • Optional remote operator panel unit can be located up to 1,000 ft. away from unit • Allows live 24-7 monitoring, performance logging, computer analysis, and secure remote control via the Internet or smart phone with PoolPak’s Virtual-Tech Technology CommandPak Specifications ®...
  • Page 11 No airflow, Blower overload, Firestat, High supply air temperature INDUSTRY LEADING FEATURES PoolPak dehumidifiers match or exceed the specifications of every other competitor in the marketplace. Built-in Refrigerant Pressure Transducers • Allow 24-7 Monitoring of critical suction and discharge pressures to ensure optimal system...
  • Page 12: Installation

    Improper lifting procedure! Test lift the unit 24 inches to verify proper operation of lifting equipment and positioning of lift points such that the unit is level. Failure to properly lift the unit could result in equipment damage, serious injury or death. PoolPak is not responsible for the improper use of ®...
  • Page 13 If the condenser is installed above the dehumidifier, ensure the hot gas line has proper oil traps. Contact PoolPak if the condenser is installed more than eight (8) feet below the dehumidifier. The installer must endeavor to ensure that all industry standards for refrigeration component installation are met.
  • Page 14 • Do not exceed 50’ total line length or install the condenser more than 8’ below the unit. Consult PoolPak before installing the outdoor air-cooled condenser more then 8 feet below or more than 50 feet away from the dehumidifier.
  • Page 15 Installation Figure 3. Typical Outdoor Condenser Installation Charging of Remote Condensers Once a proper evacuation has been accomplished the system is ready for charging. The outdoor air- cooled condenser requires a field charge by the installing contractor. The field charge required depends on the size of the condenser and the length of the piping.
  • Page 16: Field Wiring Diagram

    DRAWING NUMBER COMMENTS DATE APPROVED FWD-PCP-Z-00 FILE: PoolPak-FWD-PCP-Z-00 DFTN DATE REV #: 0.0 bsimpson 04/27/18 SHEET 1 OF 1 PCP Series Field Wiring Diagram with NC-Z/NC-B/NG-Z Remote Condenser DEHUMIDIFICATION UNIT L1 MAIN 10 ... 6 ... 1 HEAT RECOVERY PUMP ON/OFF...
  • Page 17: Remote Operator Panel

    The CPCS touch display replaces the LCD display with discrete buttons as the local and remote operator panels on PoolPak’s dehumidification systems. It uses the same communication interface as the previous operator panel and communicates over a RS-485 serial port. The touch display is modeled after the...
  • Page 18 Remote Operator Panel CommandPak Control System Touch Display ® All dimensions are in inches. Submittal 57106.1 Page 18 of 30 Nov 24, 2020...
  • Page 19: General Specification

    General Specification Part 1 - General Scope Furnish and install, where indicated, a factory-assembled, fully-enclosed, split environmental control system with energy recovery feature(s) designed for natatorium environment control Features shall include: Dehumidification by means of a direct expansion evaporator coil Space heating by means of a packaged electric resistance heating coil Cooling mode with heat rejection to a remote outdoor air cooled condenser Integral minimum outdoor air connection...
  • Page 20 General Specification Part 2 - Product General The natatorium control system shall include: Mechanical process dehumidification Indoor cabinet configuration Split system with remote outdoor air-cooled condenser for AC heat rejection A packaged electric resistance heating coil, sized as specified by the design engineer to meet the skin losses and outdoor air heating loads Air filtration via MERV-8 2-inch pleated panel filters for return and outdoor air Minimum outdoor air connection...
  • Page 21 General Specification Cabinet Construction: All cabinet 16, 20 and 24 gauge sheet metal shall be galvanized G90 steel or GalvalumeTM alloy with mill-applied zinc phosphate primer followed by an exterior grade white silicone modified polyester top coat. The sheet metal is engineered to form a cabinet with maximum strength and rigidity. All seams shall be caulked with silicone to prevent air and water leakage or infiltration The cabinet walls shall be of single-wall construction using 20 gauge pre-painted steel with 1 inch of fiberglass insulation protected by an anti-microbial top coat...
  • Page 22 General Specification Coil shall have galvanized casing and end plates Aluminum fin and copper tube joints mechanically bonded to assure high heat transfer Coils shall have a 3-year warranty extension for a total of 5 years coverage Drain Pans Each evaporator coil shall be provided with a positive draining, compound-sloped, baked powder paint coated aluminum drain pan with fully-welded corners to ensure zero water retention.
  • Page 23 General Specification installed using Schrader type valves. Refrigeration service valves shall be located outside of the airstream The receiver shall have two refrigerant level (maximum and minimum) indicating sight glasses The suction line shall be fully insulated with 0.500-inch closed cell insulation Control Panel The electrical contractor shall be responsible for external power wiring and disconnect switch fusing.
  • Page 24 General Specification Alarm - indicates there has been a failure requiring service. Dehumidification - indicates that the system is dehumidifying the space. Cooling - indicates that the air-conditioning mode. Space Heat - indicates that the space heating is operating. Maintenance - indicates whether or not maintenance is required. Manual - indicates that the system has been set to manual operation.
  • Page 25 General Specification cooled condenser. The outdoor air-cooled condenser shall be capable of rejecting 100% of the compressor heat rejection with an air-on temperature at summer design conditions. The outdoor condenser shall be equipped with 24VAC controls, including a contactor for the fan motor The system shall be provided with a dry contact rated for 5A at 24VAC to operate the remote outdoor condenser controls Each refrigeration circuit shall include refrigerant valves, a receiver with pressure relief valve set to 650 psig, a pressure control valve and a pressure differential valve, and two manual shutoff valves to isolate the outdoor condenser...
  • Page 26 General Specification Part 3 - Execution Product Delivery, Acceptance, Storage and Handling Perform a thorough physical inspection of the system upon delivery from the shipment carrier Identify and immediately report any physical damage to manufacturer If the system is to be stored prior to installation, store in a clean, dry place protected from weather, dirt, fumes, water, construction and physical damage Handle the system carefully during installation to prevent damage Damaged systems or components shall not be installed.
  • Page 27: Warranty

    Replacement Part Warranty If a replacement part provided by PoolPak under this warranty fails due to a material defect prior to the end of the Two-Year Parts Warranty (or the end of the extended warranty period if applicable), whichever comes first, PoolPak will provide a new or rebuilt part F.O.B.
  • Page 28 DASV's Customer Support team. PoolPak will not be responsible for refrigerant lost from the system due to improperly installed contractor piping to the remote outdoor air-cooled condenser.
  • Page 29 2. Optional Five-Year Dehumidifier Coil Warranty Subject to the terms above, PoolPak will provide a replacement coil for up to 60 months from the date of the warranty activation. Extended coil warranties are for parts of the dehumidifier only and does not cover parts of dry cooler or OACC coils.
  • Page 30: Factory Assisted Start-Up

    Factory Assisted Start-Up FACTORY ASSISTED START-UP The Manufacturer’s Factory technical service representative will be present on-site during the start-up for one visit only to assist the installing contractor. The representative will apply his extensive knowledge of the equipment to ensure a proper start-up and assist in making the necessary adjustments to achieve optimal operation.