Table of Content General Information ........................2 Operating Safety (Warnings, Cautions, and Notes) ................... 2 Reference and Additional Information ...................... 3 Basic Information ............................4 Dehumidifier External Systems Connection – S Cab ................. 5 Dehumidifier External Systems Connection – RH and RV cabs ..............8 Dehumidifier External Systems Connection ....................
Contact Us 1-833-DAS-POOL (327-7665) PoolPak 3491 Industrial Drive Schedule / Modify a Start-up: York, PA 17403 Startups@DehumidifiedAirServices.com Inquire about Warranty: Warranty@DehumidifiedAirServices.com PoolPak.com Order Parts: Parts@DehumidifiedAirServices.com All Other Product Support: Support@DehumidifiedAirServices.com September 2020 PoolPak PCP Series – Indoor OMM...
• Optional Pool Water Heating **. • Optional Space Heating - hot water coil, electric or gas heater ***. • Air Conditioning (AC)* – external water cooling, outdoor condenser or fluid cooler. PoolPak PCP Series – Indoor OMM September 2020...
Gas line. If the dehumidifier is equipped with a gas heater for space heating purposes, the gas line connection is to be brought to the gas heater directly. WARNING! Gas Line. The gas line must be installed in accordance with respective device documentation and local codes and regulations. September 2020 PoolPak PCP Series – Indoor OMM...
Page 7
Outdoor Air (OA) intake - top Piping Connections ① Condensate Drain ② AC – Air-Cooled (refrigeration) ③ AC – Water-Cooled (water/glycol) ④ Pool Heating Water ⑤ Space Heating Hot Water Pic. C.1-A PoolPak PCP Series – Indoor OMM September 2020...
Page 8
Outdoor Air (OA) intake ductwork connection options – top, horizontal. Piping Connections ① Condensate Drain ② AC – Air-Cooled (refrigeration) ③ AC – Water-Cooled (water/glycol) ④ Pool Heating Water ⑤ Space Heating Hot Water Pic. C.1-B September 2020 PoolPak PCP Series – Indoor OMM...
Gas line. If the dehumidifier is equipped with a gas heater for space heating purposes, the gas line connection is to be brought to the gas heater directly. WARNING! Gas Line. The gas line must be installed in accordance with respective device documentation and local codes and regulations. PoolPak PCP Series – Indoor OMM September 2020...
Page 10
Mirrored Arrangement Both, horizontal and vertical, dehumidifier could have standard and mirrored cabinet arrangement (see Pic.C.2). Note, that all options and details, described above, apply to both, standard and mirrored arrangement. Pic. C.2 September 2020 PoolPak PCP Series – Indoor OMM...
Page 11
– top, horizontal side (left or right). Piping Connections ① Condensate Drain ② AC – Air-Cooled (refrigeration) ③ AC – Water-Cooled (water/glycol) ④ Pool Heating Water ⑤ Space Heating Hot Water Electrical connection Pic. C.1-A PoolPak PCP Series – Indoor OMM September 2020...
Page 12
• Optional Pool Water Heating **. • Optional Space Heating - hot water coil, electric or gas heater ***. • Air Conditioning (AC)* – external water cooling, outdoor condenser or fluid cooler. September 2020 PoolPak PCP Series – Indoor OMM...
Gas line. If the dehumidifier is equipped with a gas heater for space heating purposes, the gas line connection is to be brought to the gas heater directly. WARNING! Gas Line. The gas line must be installed in accordance with respective device documentation and local codes and regulations. PoolPak PCP Series – Indoor OMM September 2020...
Page 14
Dehumidifier Optional Arrangement. Two-Compressor Arrangement Standard PCP series dehumidifier has one compressor, however two-compressor arrangement is available also. Note, that all options and details, provided above, apply to both, standard and two-compressor arrangement: • Single Deck dehumidifier has same dimensions,...
Page 15
Proper clearances should be maintained for adequate airflow and heat rejection! Generally, up to 36” side and 96” top clearances are required. For more information on clearances as well as equipment dimensions and other details, refer to the submittal documentation. PoolPak PCP Series – Indoor OMM September 2020...
D.1B-RH, D.1A-BV and D.1A-BH below show all/most available options, some of which may not be present on your dehumidifier. Dehumidifier Main Components – S cab Pic. D.1-S • Main Blower (1) is in the main blower compartment next to the Main Electric Panel (2) and Compressor Compartment (3). September 2020 PoolPak PCP Series – Indoor OMM...
Page 19
If the dehumidifier has the water-cooled air conditioning option (equipped with fluid cooler or connected to external water-cooling source), the compressor circuit also includes the plate heat exchanger (16)). • Main Electric Panel contains Main Control Board (17), Operator Panel (18) and other electrical components. PoolPak PCP Series – Indoor OMM September 2020...
Dehumidifier Main Components – RV and RH Cabs RV Cab Pic. D.1A-RV September 2020 PoolPak PCP Series – Indoor OMM...
Page 21
Hot water coil is usually located directly downstream of the reheat coil; Electric heater is usually mounted directly on the dehumidifier’s supply air duct connection. Gas heater (duct heater or boiler package) normally is installed externally (not shown). PoolPak PCP Series – Indoor OMM September 2020...
Page 22
Feasible field installation options include OP mounting plate (18) on the corner post or elsewhere in mechanical room or maintenance office (see Interface and Communication for details). September 2020 PoolPak PCP Series – Indoor OMM...
Page 23
Dehumidifier Main Components – BV and BH cabs Pic. D.1A-BV PoolPak PCP Series – Indoor OMM September 2020...
Page 24
Hot water coil is usually located directly downstream of the reheat coil; Electric heater is usually mounted directly on the dehumidifier’s supply air duct connection. Gas heater (duct heater or boiler package), if provided, normally is installed externally (not shown). September 2020 PoolPak PCP Series – Indoor OMM...
(25) and Pool Out (26)) measure the entering and leaving pool water temperature. The sensors are located directly at the respective connections of the coaxial pool water heat exchanger. As an option, the pool water heat exchanger piping/manifold may have water flow switch also. PoolPak PCP Series – Indoor OMM September 2020...
Page 26
It may also be located in main electrical panel or in the dehumidifier in general. Pic. D.4-S September 2020 PoolPak PCP Series – Indoor OMM...
Page 27
Pic. D.4-R PoolPak PCP Series – Indoor OMM September 2020...
Page 28
Pic. D.4-B September 2020 PoolPak PCP Series – Indoor OMM...
Page 29
Depending on the type, size and installation, outdoor condensers may be provided with different set of legs/supports (34), which are required assembly on-site – refer to the Installation manual. PoolPak PCP Series – Indoor OMM September 2020...
Page 30
The pump package electrical sub-panel (40) contains the pump package electrical power and control apparatuses. • The pump package manifolds are usually equipped with pressure gauges, automatic air venting valve, draining and other valves. NG-Z NG-V Pic. D.6 September 2020 PoolPak PCP Series – Indoor OMM...
If pool water is needed to be warmed up – more heat is diverted towards pool heating coaxial heat exchanger (if dehumidifier is equipped with this option). • Rest of the heat (if any) is diverted towards outdoors (outdoor condenser, fluid cooler, etc.) PoolPak PCP Series – Indoor OMM September 2020...
Page 32
– pump would stay engaged while fans are engaged (regardless of the fans’ speed). September 2020 PoolPak PCP Series – Indoor OMM...
(the alarm that’s locked out the device or entire dehumidifier). For detailed information on TouchDisplay OP refer to CommandPak® Control System Touch Display User Manual, provided with the dehumidifier (or contact factory to obtain a copy). PoolPak PCP Series – Indoor OMM September 2020...
Page 34
For more details regarding alarms and alerts, refer to the Alarms Description information (available via Help feature in Touch Display OP); contact factory if needed. September 2020 PoolPak PCP Series – Indoor OMM...
LonWorks Gateway for communication purposes. For more information about Web Monitor or BMS communication set up (connection, configuration, access, point cutsheets, etc.) – contact factory. Pic. F.2 PoolPak PCP Series – Indoor OMM September 2020...
Basic Maintenance Although PoolPak equipment is built for minimal service downtime, periodic preventative maintenance is required to ensure maximum reliability, safety, and operating efficiency. WARNING! To ensure equipment longevity and proper and efficient operation, the dehumidifier and its auxiliary systems and devices (outdoor condenser, fluid cooler, boiler package, etc.) must be maintained properly and regularly.
Page 37
Check gasket condition on all doors to ensure an airtight seal Check bolts on compressors, motor mounts, dehumidifier bases and coils and tighten if required Verify that the airflow around the remote condenser or dry cooler is unobstructed PoolPak PCP Series – Indoor OMM September 2020...
Straighten any coil fins that have been bent during the cleaning process • Confirm the drain line is clear • Replace all panels and parts and restore electrical power to the equipment September 2020 PoolPak PCP Series – Indoor OMM...
Email: Warranty@DehumidifiedAirServices.com PoolPak warrants as set forth and for the time periods shown below that it will provide through either a DASV Service Technician or an authorized service organization specified and approved by DASV, a new or rebuilt part to replace a factory installed part which has failed because of defect in workmanship or material.
Page 41
Replacement Part Warranty If a replacement part provided by PoolPak under this warranty fails due to a material defect prior to the end of the Two-Year Parts Warranty (or the end of the extended warranty period if applicable), whichever comes first, PoolPak will provide a new or rebuilt part F.O.B.
Page 42
2. Optional Five-Year Dehumidifier Coil Warranty Subject to the terms above, PoolPak will provide a replacement coil for up to 60 months from the date of the warranty activation. Extended coil warranties are for parts of the dehumidifier only and does not cover parts of dry cooler or OACC coils.