Communications gateway module installation kit
Hide thumbs Also See for 24J415:
Table of Contents

Advertisement

Available Internal Data
Units
Tank Blue
1 = Filling, 0 = Off
Fill
Tank Red
1 = Filling, 0 = Off
Fill
12
CGM Input
In
from PLC
Out
Byte
Output
Byte
Bit 1 = 1, Blue
Tank heat
enable
Bit 2 = 1, Red
Inline heat
enable
Bit 3 = 1, Blue
Inline heat
enable
Bit 4 = 1, Red
Hose heat
enable
Bit 5 = 1, Blue
Hose heat
enable
Bit 6 = 1, Red
Chiller heat
enable
Bit 7 = 1, Blue
Chiller heat
enable
7
Tank Fill Not
Active = 0
Begin Tank Fill-
ing = 1
8
Tank Fill Not
Active = 0
Begin Tank Fill-
ing = 1
CGM Output
to PLC Input
Bit 1 = 1, Blue
Tank heat ON
Bit 2 = 1, Red
Inline heat ON
Bit 3 = 1, Blue
Inline heat ON
Bit 4 = 1, Red
Hose heat ON
Bit 5 = 1, Blue
Hose heat ON
Bit 6 = 1, Red
Chiller ON
Bit 7 = 1, Blue
Chiller ON
7
Tank not Fill-
Initiates a fill valve open. This bit
ing = 0
can be used to initiate a manual fill
cycle or a auto fill cycle if the auto fill
Tank Filling =
mode is selected. The tank fill valve
1
will close upon reaching the high
level switch. See Byte 79 for tank
level status. If the Tank fill bit is
maintained the GCA will close the
valve when the tank is full. Auto time
out and alarm if the Hi level is not
reached within a preset time.
8
Tank not Fill-
Initiates a fill valve open. This bit
ing = 0
can be used to initiate a manual fill
cycle or a auto fill cycle if the auto fill
Tank Filling =
mode is selected. The tank fill valve
1
will close upon reaching the high
level switch. See Byte 79 for tank
level status. If the Tank fill bit is
maintained the GCA will close the
valve when the tank is full. Auto time
out and alarm if the Hi level is not
reached within a preset time.
Descriptions
3A1704H