Operating Modes; 0- Program; 1- Status; 2- History - Bosch FPT-DACT Operations & Installation Manual

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide | 5.0 Programming
5.5

Operating Modes

The FPT-DACT operating modes are Program, Status,
History, Test, and Reset. Each mode appears as an
option on the FPT-DACT's Main Menu.
SYSTEM NORMAL

0- PROGRAM

1- STATUS

2- HISTORY

3- TEST

4- RESET

5.5. 1
0- PROGRAM
When the FMR-DACT-KEYPAD is connected to the
FPT-DACT, the Main Menu appears a short time after
the keypad starts up. Refer to
page 28 for programming instructions.
5.5.2
1- STATUS
When you select 1- STATUS, the top line shows the
highest priority off-normal condition. The second line
shows each off-normal condition sequentially.
Press [* Clear] to finish the Status Mode and returns to
the Main Menu.
5.5.3
2- HISTORY
When you select 2- HISTORY, the most recent event in
the history log appears. Refer to
page 26 for a detailed description of History Mode
operation.
5.5.4
3- TEST
Do not select 2: TEST TONES. This
selection is for factory testing only.
When you select 3- TEST, the window shows the test
items:
TEST MODES
1: TEST COMM
2: TEST TONES
1: TEST COMM
To access TEST COMM, select [3]: TEST--->[1]: TEST
COMM. Selecting this option allows you to initiate a
Manual Communications Test.
1/05 | F01U002505B
on
Section 5.0 Programming
on
Section 4.4.4 History
To initiate a Manual Communications Test:
1. At the Main Menu, press [3] to select 3: TEST. The
Test Modes window appears.
2. Press [1] to select 1: TEST COMM. The window
shows:
SEL PHONE LINE
1: LINE 1
2: LINE 2
3: ALTERNATE
The ALTERNATE option uses the phone line
not used in the previous Comm Test.
3. Select the appropriate line to be tested, LINE 1 or
LINE 2. You can also press [* Clear] to end testing.
Once a line is selected, a Manual Communications
Test is initiated and the window shows:
C O M M U N I C A T O R
LINE 1, TRY 1
The bottom line indicates the line on which the
Manual Communications Test was initiated and the
current attempt (try). The FPT-DACT makes up to
two attempts before declaring a failure. When the
FPT-DACT declares a failure, the window shows:
COMMUNICATOR
FAILED
This message appears briefly, then the LCD returns
to the Test Modes Menu.
If the Manual Communications Test passes, the
window shows:
COMMUNICATOR
PASSED
This message appears briefly, and then the LCD
returns to the Test Modes Menu.
For more information about the types of
communications tests the FPT-DACT can
perform, refer to Section 4.1.9
Communications Tests on page 21.
5.5.5
4- RESET
You can manually reset the FPT-DACT by either
selecting RESET from the Main Menu or pressing
[Reset] on the FMR-DACT-KEYPAD.
Refer to
on page 26 for a description on
Section 4.5 Reset
resetting the FPT-DACT.
EN | 44