Prog Deflts; Slave Conectn - Bosch FPT-DACT Operations & Installation Manual

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide |
5.4.7

PROG DEFLTS

PROG DEFLTS
1: CLEAR HISTORY
2: DEFAULT ALL EE
3: DEFLT 4/2 CDES
The PROG DEFLTS feature clears the history logger,
resets the FPT-DACT to its default EEPROM settings,
and applies default reporting codes.
1: CLEAR HISTORY
To access CLEAR HISTORY, select [0]: PROGRAM
--->[7]: PROG DEFLTS--->[1]: CLEAR HISTORY.
You can clear some or all of the history records in the
system using this option.
To clear the history logger, reset the FPT-DACT to
default settings, and apply default reporting codes:
1. At the Prog Defaults Submenu, press [1] to select
1: CLEAR HISTORY. The window shows:
HIST ITEMS= _____
DEL OLDEST ###
2. The number on the first line shows the total number
of records stored in the history logger. Enter the
number of history records you want to delete and
press [# Command]. Those events are erased and
the FPT-DACT returns to the Prog Defaults Menu.
2: DEFAULT ALL EE
To access DEFAULT ALL EE, select [0]: PROGRAM
--->[7]: PROG DEFLTS--->[2]: DEFAULT ALL EE.
This option allows you to set the FPT-DACT to the
original factory programming configuration.
All programming, including the point
configurations and option selections, is lost
when this operation is performed.
The Date/Time settings are not affected
when setting the FPT-DACT to the default
settings.
To set the FPT-DACT to the original factory
programming configuration:
1. At the Prog Defaults Submenu, press [2] to select
2: DEFAULT ALL EE. The window shows:
DEFAULT EE?
NO: YES (1)/NO (0)
2. The entry preceding the colon (:) on the second line
indicates the current setting. To restore the
FPT-DACT to its factory settings, press [1] and
[# Command].
1/05 | F01U002505B
5.0 Programming
3. Then press [* Clear]. The window shows:
When the operation is complete, the Prog Defaults
Submenu reappears.
3: DEFLT 4/2 CDES
To access DEFLT 4/2 CDES, select [0]: PROGRAM
--->[7]: PROG DEFLTS--->[3]: DEFLT 4/2 CDES.
This option sets all of the programming for 4/2 codes to
the default.
To set all 4/2 code programming to the default:
1. At the Prog Defaults Submenu, press [3] to select
3: DEFLT 4/2 CDES. The window shows:
2. The entry preceding the colon (:) on the second line
indicates the current setting. To default 4/2 reports,
press [1] followed by [# Command]. Pressing
[* Clear] shows:
When the operation is complete, the Prog Defaults
Submenu reappears.
5.4.8
The SLAVE CONECTN feature allows you to program
parameters for the serial connection to the control panel.
To access SLAVE CONECTN, select [0]: PROGRAM
---> [8]: SLAVE CONECTN.
The system can be programmed with a bus address. If
the connection is to be supervised, the bus address on the
keypad programmer must match the control panel's bus
address. The normal default value of 32 is acceptable.
SETTING EEPROM
TO DEFAULT...
DEFLT 4/2 CDES?
NO: YES (1)/NO (0)
SETTING EEPROM
TO DEFAULT...

SLAVE CONECTN

SLAVE CONECTN
1: BUS ADDRESS
2: SUPERVISE BUS
EN | 43