Bosch FPT-DACT Operations & Installation Manual page 50

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide | Appendix C
Table 11: continued
Report
SIA
Description
Code
Phone 2 Trouble
LT 2
Phone 2 Restore
LR 2
System Trouble
IA
System Trouble
IR
Restore
Fire Drill Start
FI
Fire Drill End
FK
System Test
TS
System Test
TE
Restore
Silence
KB
Manual Test
RX
Data Lost
RT
EEPROM Failure
IA 4
Trouble Input
IA 2
Trouble Input
IR 2
Restore
System Trouble
IA 5
Keypad
System Restore
IR 5
Keypad
System Trouble
IA 6
Comm Fault
System Restore
IR 6
Comm Fault
System Trouble
IA 11
Programming
System Restore
IR 11
Programming
Serial
Communication
YC
Fault
Serial
Communication
YK
Restore
Refer to Notes 1 through 9 on page 52.
* In Modem IIIa2, the FPT-DACT uses Communications Fail to report a Data Lost event. The FPT-DACT reports an Equipment Fail
and Equipment Fail Restore with Condition 006 to report an actual Communications Fault.
1/05 | F01U002505B
Point-Related Events
SIA
Contact ID
Description
Code
Phone Line
1 352 aa 000
Trouble
Phone Line
3 352 aa 000
Restoral
Equipment Failure
1 300 aa 000
Condition
Equipment Fail
3 300 aa 000
Restoral
Fire Test Begin
1 607 00 000
Fire Test End
3 607 00 000
Test Start
1 607 aa 000
Test End
3 607 aa 000
Heat/Bypass
1 607 aa 000
Manual Test
1 601 aa 000
Data Lost
1 354 aa 000
Equipment Failure
1 307 aa 000
Condition
Equipment Failure
1 300 aa 002
Condition
Equipment Fail
3 300 aa 002
Restoral
Equipment Failure
1 300 aa 005
Condition
Equipment Fail -
3 300 aa 005
Restoral
Equipment Failure
1 300 aa 006
Condition
Equipment Fail
3 300 aa 006
Restoral
Equipment Failure
1 300 aa 011
Condition
Equipment Fail
3 300 aa 011
Restoral
Communications
1 350 aa 000
Fail
Communications
6 350 aa 000
Restoral
4/2 Code
Contact ID
Default
Description
Values
Telco 2 Fault
FC
Telco 2 Fault
EC
System Trouble
FD
System Trouble
ED
Walk Test
F2
Mode
Walk Test
E2
Mode Restore
Walk Test
26
Mode
Walk Test
27
Mode Restore
Open/Close
1F
Manual Trigger
FE
Test
Fail to
FF
Communicate
Self Test
FD
Failure
System Trouble
FD
System Trouble
ED
System Trouble
FD
System Trouble
ED
System Trouble
FD
System Trouble
ED
System Trouble
FD
System Trouble
ED
Communication
FD
Trouble
Communication
Trouble
ED
Restoral
EN | 50
2
Modem IIIa
Description
Phone Line Fail
Phone Line = 2
Phone Line Restoral
Phone Line = 2
Equipment Fail
Equipment Restoral
Fire Walk Start
ID: 0000
Fire Walk End
ID: 0000
Walk Test Start
Walk Test End
Alarm Silence
Test Report Non
Expanded
Communications
Fail *
Parameter Checksum
Fail
Equipment Fail
COND = 002
Equipment Restoral
COND = 002
Equipment Fail Cond
= 005
Equipment Restoral
Cond = 005
Equipment Fail Cond
= 006
Equipment Restoral
Cond = 006
Equipment Fail Cond
= 011
Equipment Restoral
Cond = 011
Comm Fail,
RG = 1
Comm Fail
Restr = RG1