History; Reset; Figure 22: Submenu Items; Figure 23: Event History Example - Bosch FPT-DACT Operations & Installation Manual

Fire communicator
Table of Contents

Advertisement

FPT-DACT | Operation & Installation Guide | 4.0 System Operation
Submenu Items: The corresponding key to a submenu
item can appear in the second line preceding a colon.
Press the corresponding key to select that item. For
example, press [1] to select PROG TIME from the
Programming Mode Menu (Figure 22).

Figure 22: Submenu Items

1 -
Corresponding key
When a scrolling menu is active, it is not
necessary to wait for the desired menu item
to appear before making your selection. You
can select any item on the current menu
rotation at any time.
4.4.4

History

The history buffer can be cleared when the
system loses all power for more than
3 min.
The History option accesses a list of system events that
occurred. To select History, press [2] from the Main
Menu or press [History] on the keypad.
A maximum of 100 events can be stored in the history
buffer.
Once you enter the History Mode, the most recent
system event appears on the top line of the FMR-DACT-
KEYPAD LCD. The time and date appears on the
second line. As a reminder, the bottom line toggles
every 4 sec between the time and date the event
occurred and the keys used to navigate through the
history buffer. Refer to
Figure 23.
Navigate the history buffer by pressing the following
FMR-DACT-KEYPAD keys:
[Disable] moves to older events in the history buffer.
[Drill] moves to newer events in the history buffer.
[* Clear] finishes the History Mode and returns to
the Main Menu.
Table 8 on page 27 lists the event history abbreviations.
Events received from an analog FACP over
the serial connection are not stored in the
history buffer.
1/05 | F01U002505B

Figure 23: Event History Example

1 - Total number of stored events
2 - Event #
3 - Event
4 - Time
5 - Month
6 - Day
7 - Year
8 - Press [Drill] to advance to the next event.
9 - Press [Disable] to show the previous event.
4.5

Reset

You can manually reset the FPT-DACT in one of four
ways:
1. On the FMR-DACT-KEYPAD, press [4] to select
Reset from the Main Menu or press [Reset]. Press
either key to reset the FPT-DACT only if off-normal
conditions are present. The system sends an Open
Reset Report with the user ID parameter of 99.
2. Exiting the Test Mode. The system sends an Open
Reset Report with the user ID parameter of 99.
3. Exiting the Programming Mode. The system sends
an Open Reset Report with a user ID parameter of
01.
4. Powering up the FPT-DACT. No Open Reset Report
is sent.