Pulse counter logic for metering (PC)
Chapter 13
Verifying settings by secondary
injection
20
Pulse counter logic for metering (PC)
The test of the pulse counter function requires at least the PST Parameter Setting Tool or SPA
(or LON) connection to a station HMI including corresponding functionality. A known number
of pulses are with different frequency connected to the pulse counter input. The test should be
performed for the settings operation = Off/On and for blocked/deblocked function. The pulse
counter value is then read by the PST or station HMI.