32.1.4
158
Residual overcurrent protection (ROCP)
6.
Change the level of the injected current and measure the operating
time of the ROCP function. Use the ROCP_TRHIGH signal. Compare
this operating time with the set value tHigh
Completing the test
Continue to test another function or complete the test by setting the test mode off.