Volvo Penta TAD1360VE Operator's Manual page 34

Table of Contents

Advertisement

Instruments and Controls
32
Setup
parameter setting in the engine's control systems.
Different menus appear under Customer parameter,
depending on whether Versatile or Gen set has been
selected from Set application. See below.
The parameters that can be set/selected (choice is
made with the SEL button) are:
Set application, setting Versatile or Gen set.
Depending on the selection made here, different
menus will appear under Customer parameter.
Unit, setting of units (metric or US imperial).
Language, setting the language used on the
display. Choose between English, French, German
and Spanish.
Stop energized to, setting of external stop input.
Activated by Stop or Run.
Stop: The stop input must be connected to voltage
to stop the engine.
Run: The stop input must be connected to voltage
to run the engine.
Customer parameter, setting alarm limits. Refer to
Customer parameter / Versatile and Customer
parameter / Gen set.
Throttle input setting, setting of engine-speed
control and voltage limits. Refer to Throttle input
setting.
Display setting, setting the display. refer to Display
setting.
Customer parameter / Versatile
Idle engine speed - setting idle speed.
Preheat on ignition - activation of automatic pre-
heating. The engine control system senses if pre-
heating is needed and activates it directly at switch-
on.
Governor gradient (Nm/rpm) - setting of droop
level, when activated. For activation, refer to
Governor droop in the main menu.
Oil temp warning limit (°C) - setting alarm limit for
oil temperature.
Coolant temp warning limit (°C) - setting alarm
limit for coolant temperature.
47711155 06-2021 © AB VOLVO PENTA