1397 Enhanced Field Supply Card
Installation, Cont'd
— Top —
40-75 HP/230V Drives
75-150 HP/460V Drives
DANGER
CIRCUIT BREAKER DOES NOT DISCONNECT INCOMING A0
LINE POWER IT ONLY PROVIDES DC FAULT PROTECTION.
LE DISCONECTEUR NE COUPTE PAS L'AUTOMENTATION DU SPOTEUR IL NES
SERT QUE A ASSURER UNE PROTECTION CONTRE LES DESFAULTS DC.
DANGER
!
RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT
POWER BEFORE SERVICING EQUIPMENT.
GND
TORQUE
14-10GA 35 LB.-IN.
0 GA 48 LB.-IN.
SPEC
— Front —
100-150 HP/230V Drives
200-300 HP/460V Drives
1397-5.24 March, 2005
❏ 9 Replace fuses 6FU, 7FU
CC/600V/25A fuses included with the kit.
Locate the replacement fuse table on the back of the carrier.
Attach one of the adhesive fuse rating labels (P/N 179540) over
the 600V 15A designations as shown in the illustration.
6FU 7FU 8FU
6FU 7FU 8FU
8FU with the (3) UL class
&
— Top —
1.5-30 HP/230V Drives
3-60 HP/460V Drives
6FU 7FU 8FU
— Inside Right Side Panel —
400-600 HP/460V Drives