Label Replacement - Allen-Bradley 1397 Installation Instructions Manual

Enhanced field supply
Hide thumbs Also See for 1397:

Advertisement

Label
Replacement
Installation, Cont'd
Setup
1397 Enhanced Field Supply Card
Typical Fuse Label Replacement
(3 to 60 HP @ 460 VAC Drives Shown)
❏ 10 If required, reinstall the auxiliary panel cover or AC line
disconnect removed in steps 4a & 4b. Torque the (3) bus bar
fasteners to the values listed below.
Fastener Size
1
/
"
4
3
/
"
8
(3) drive parameters, Jumper 21 on the drive's Regulator Board, and
the Enhanced Field Supply Card's jumper wire must be set to configure
the Enhanced Field Supply Card. The J21 Jumper on the Regulator
Board must be set to the same setting as the Enhanced Field Supply.
P.050 — Nominal AC Freq
This parameter must be set to match the AC input line's frequency.
P.273 — Fld Econ Delay
Some motor fields may not be able to withstand the power dissipated
under full field voltage with the motor stopped. Parameter
allows a fixed reduction of field voltage to be set
P.273 [Fld Econ Delay]
for a user specified amount of time while the motor is stopped. When
restarted, the motor will be returned to the full field output voltage
level set by
P.272 [E-Fld Volts Adj]
600V 25A
Maximum Torque
7.46 N-m (66 lb.-in.)
26.66 N-m (236 lb.-in.)
.
1397-5.24 March, 2005
9