Configuration

11.5.4 Additional zone

Installer reference guide
168
#
Code
[2.C.1]
[8‑05]
[2.C.2]
[8‑06]
INFORMATION
When leaving water temperature modulation is enabled, the weather‑dependent
curve needs to be set to a higher position than [8-06] plus the minimum leaving
water temperature setpoint required to reach a stable condition on the comfort
setpoint for the room. To increase efficiency, modulation can lower the leaving water
setpoint. By setting the weather‑dependent curve to a higher position, it cannot drop
below the minimum setpoint. See the illustration below.
T t
+[8-06]
−[8-06]
a Weather-dependent curve
b Minimum leaving water temperature setpoint required to reach a stable condition
on the comfort setpoint for the room.
WD curve type
The weather-dependent curve can be defined using the 2-points method or the
Slope-Offset method.
See
"11.4.2 2-points
curve" [
#
Code
[2.E]
N/A
Setpoint screen
Control the leaving water temperature for the additional zone via setpoint screen

[3] Additional zone.

See
"11.3.5 Setpoint
screen" [
Schedule
Indicates if the desired leaving water temperature is according to a schedule.
See
"11.5.3 Main
zone" [
Modulation:
0 No (disabled)
1 Yes (enabled)
Note: The desired leaving water temperature
can only be read out on the user interface.
Max modulation:
0°C~10°C
This is the temperature value by which the
desired leaving water temperature is increased or
decreased.
a
b
T a
4
 153] and
"11.4.3 Slope-offset
2-points
Slope-Offset
4
 147].
4
 161].
Description
4
curve" [
 154].
Description
EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04